Troubleshooting and Error Codes
1-9
59
Net Loss DPI P5
A communications fault has occurred
between the communication adapter
at DPI port 5 and the network.
•
Verify network connection.
•
Verify status of network.
•
Configured with parameter 392
[NetLoss DPI Cnfg]
60
Net Loss DPI P6
A communications fault has occurred
between the communication adapter
at DPI port 6 and the network.
•
Verify network connection.
•
Verify status of network.
•
Configured with parameter 392
[NetLoss DPI Cnfg]
61
Logix Out of Run
The DriveLogix controller is in a
Non-Run mode. Non-Run modes
include program, remote-program
and faulted modes.
•
Clear fault
•
Configured with parameter 386
[Lgx OutOfRunCnfg]
62
Logix Timeout
The communication connection to the
DriveLogix controller has timed out.
Configured with parameter 387 [Lgx
Timeout Cnfg]
63
Logix Closed
The DriveLogix controller has closed
the Controller to
Drive connection.
•
Verify drive is present in I/O
•
Configured with parameter 388
[Lgx Closed Cnfg]
64
Logix Link Chng
A required link in the Controller to
Drive Communication Format has
been modified.
•
Clear fault
•
Configured with parameter 389
[Lgx LinkChngCnfg]
65
HiHp In PhaseLs
AC Input Phase Loss - the AC input
phase voltage has fallen.
1. Check for voltage on each AC
input phase.
2. Check the status of each external
AC input fuse.
3. Check the Rectifying board and
Rectifying Modules for each AC
input phase.
4. Configured with parameter 370
[HiHp InPhsLs Cfg]
66
HiHp Bus Com Dly
(High Horse Power Only)
Bus Communication Time Delay - the
communication bus has delayed
feedback, or bad communication
quality.
Check the communication bus lines:
•
10 pin connector between the
Main Control board and High
Power Fiber Optic Interface board.
•
Fiber-optic connections between
the High Power Fiber Optic
Interface Circuit board and the
ASIC board.
•
Fiber-optic connections between
the High Power Fiber Optic
Interface board and Voltage
Feedback board
67
HiHp Bus Link Ls
Bus Communication Link Loss - bus
communication between the High
Power Fiber Optic Interface circuit
board and the Voltage Feedback
circuit board has stopped.
Check the communication bus lines:
•
Fiber-optic connections between
the High Power Fiber Optic
Interface board and Voltage
Feedback board
•
10 pin connector between the
Main Control board and High
Power Fiber Optic Interface board
•
Fiber-optic connections between
the High Power Fiber Optic
Interface Circuit board and the
ASIC board
No. Name
Description
Action
(if appropriate)
Содержание powerflex 700h
Страница 4: ...soc ii Summary of Changes Notes ...
Страница 8: ...4 ...
Страница 46: ...2 14 Component Test Procedures ...
Страница 92: ...3 46 Access Procedures Notes ...
Страница 98: ...A 2 Service Tools and Equipment Notes ...
Страница 106: ...B 8 Schematics Notes ...
Страница 116: ...C 10 Disassembly Assembly Diagrams Notes ...
Страница 119: ......