Nrdy_Disabled
BOOL
1 = Device not ready due to the following:
•
Device disabled by Maintenance
•
Configuration error
•
Interlock not OK
•
Permissive not OK
•
Operator Stop priority command requires reset
•
Device failure (shed requires reset),
•
I/O Fault (shed requires reset)
•
Device tripped (Drive Fault)
•
Drive not ready
•
Device logic disabled/no mode.
Nrdy_CfgErr
Nrdy_Intlk
Nrdy_Perm
Nrdy_OperPrio
Nrdy_Fail
Nrdy_IOFault
Nrdy_Trip
Nrdy_DriveNR
Nrdy_NoMode
Sts_MaintByp
BOOL
1 = Maintenance bypass is active, display icon.
Sts_AlmInh
BOOL
1 = Alarm is shelved, disabled, or suppressed, display icon.
Sts_MsgErr
BOOL
1 = Message error, unable to read at least one non-RPI drive parameter.
Sts_Err
BOOL
1 = Error in configuration: See detail bits for reason.
Err_Timer
BOOL
1 = Error in configuration: Invalid check or reset pulse time (use 0…2,147,483).
Err_Sim
BOOL
1 = Error in configuration: Simulation timer preset (use 0…2,147,483).
Err_Alarm
BOOL
1 = Error in configuration: Alarm minimum On time or severity.
Err_FdbkEU
BOOL
1 = Error in configuration: Speed Fdbk EU Min = Max.
Err_RefLim
BOOL
1 = Error in configuration: Speed Ref Limit Min > Max.
Err_RefEU
BOOL
1 = Error in configuration: Speed Ref EU Min = Max.
Sts_Hand
BOOL
Mode.Sts_Hand
1 = Mode is Hand (supersedes Maintenance, Override, Program, Operator).
Sts_Maint
BOOL
Mode.Sts_Maint
1 = Mode is Maintenance (supersedes Override, Program, Operator).
Sts_Ovrd
BOOL
Mode.Sts_Ovrd
1 = Mode is Override (supersedes Program, Operator).
Sts_Prog
BOOL
Mode.Sts_Prog
1 = Mode is Program (auto).
Sts_Oper
BOOL
Mode.Sts_Oper
1 = Mode is Operator (manual).
Sts_ProgOperLock
BOOL
Mode.Sts_ProgOperLock
1 = Program or Operator has requested mode lock.
Sts_NoMode
BOOL
Mode.Sts_NoMode
1 = No mode (disabled because EnableIn is false).
Sts_MAcqRcvd
BOOL
Mode.Sts_MAcqRcvd
1 = Maintenance acquire command received this scan
Sts_FailToStart
BOOL
FailToStart.Inp
1 = Drive failed to start.
Sts_FailToStop
FailToStop.Inp
1 = Drive failed to stop.
Sts_IntlkTrip
IntlkTrip.Inp
1 = Drive was stopped by an interlock not OK (one-shot).
Sts_DriveFault
DriveFault.Inp
1 = Drive Fault (see drive display or manual).
Sts_IOFault
IOFault.Inp
I/O Communication fault status:
0 = OK
1 = Bad
Ack_FailToStart
BOOL
FailToStart.Ack
1 = Fail to Start, Fail to Stop, Interlock Trip, Drive Fault, or I/O Fault alarm has been
acknowledged.
Ack_FailToStop
FailToStop.Ack
Ack_IntlkTrip
IntlkTrip.Ack
Ack_DriveFault
DriveFault.Ack
Ack_IOFault
IOFault.Ack
Table 9 - P_PF7000 Drive Output Parameters
Output Parameter
Data Type
Alias For
Description
Содержание PowerFlex 7000
Страница 1: ...Rockwell Automation Library of Process Objects PowerFlex 7000 Drive P_PF7000 Reference Manual ...
Страница 4: ...4 Rockwell Automation Publication SYSLIB RM056B EN P February 2017 Table of Contents Notes ...
Страница 66: ...66 Rockwell Automation Publication SYSLIB RM056B EN P February 2017 PowerFlex 7000 Drive P_PF7000 Notes ...
Страница 67: ......