50
Rockwell Automation Publication SYSLIB-RM056B-EN-P - February 2017
PowerFlex 7000 Drive (P_PF7000)
Time after Stop to
drop Run Feedback
before Fault (sec)
Type the amount of time to allow for
the drive’s run feedback to confirm
the drive has stopped before raising a
Fail to Stop alarm.
Configuration
and Tuning
Maintenance
(Code D)
Cfg_FailToStopT
Maximum jog time
(sec) 0 = unlimited
Type the maximum time (in seconds)
that the drive can be jogged by using
OCmd_Jog.
IMPORTANT:
This value stops drive
jogging if HMI communication is lost
during a jog.
Cfg_MaxJogT
Speed Reference
Limits (Minimum
and Maximum)
Type the clamping limits for the
speed reference. If a speed reference
outside this range is entered, the
speed is clamped at these limits and
Sts_SpeedLimited is asserted.
•
Cfg_MaxSpdRef
•
Cfg_MinSpdRef
Table 15 - Maintenance Tab Page 2 Description
Function
Action
Security
Configuration Parameters