Rockwell Automation Publication SYSLIB-RM056B-EN-P - February 2017
PowerFlex 7000 Drive (P_PF7000)
Cfg_OCmdResets
BOOL
0
1 = New Operator drive command resets latched shed conditions.
0 = Reset required to clear shed conditions.
Cfg_OvrdPermIntlk
BOOL
0
1 = Override ignores bypassable permissives/interlocks.
0 = Always use permissives/interlocks.
Cfg_ShedOnFailToStart
BOOL
1
1 = Stop motor and alarm on Fail to Start.
0 = Alarm only on Fail to Start.
IMPORTANT:
If a condition is configured to shed the device to the Off state on a
fault, a reset is required to clear the shed fault to command the drive to a state
other than Off.
Cfg_ShedOnIOFault
BOOL
1
1 = Stop motor and alarm on I/O Fault.
0 = Alarm only on I/O Fault.
IMPORTANT:
If a condition is configured to shed the device to the Off state on a
fault, a reset is required to clear the shed fault to command the drive to a state
other than Off.
Cfg_SimScaleEU
BOOL
0
1 = In simulation, scale Speed Ref EU to Speed Fdbk EU.
Cfg_SimScaleRaw
BOOL
0
1 = In simulation, scale Speed Ref EU to raw, then raw to Speed Fdbk EU.
Cfg_HasFailToStartAlm
BOOL
FailToStart.Cfg_Exists
0
These parameters determine whether the corresponding alarm exists and is
checked or if the alarm does not exist and is not used. When these parameters are
1, the corresponding alarm exists.
Cfg_HasFailToStopAlm
FailToStop.Cfg_Exists
Cfg_HasIntlkTripAlm
IntlkTrip.Cfg_Exists
Cfg_HasDriveFaultAlm
DriveFault.Cfg_Exists
Cfg_HasIOFaultAlm
IOFault.Cfg_Exists
Cfg_FailToStartResetReqd
BOOL
FailToStart.Cfg_ResetReqd
0
These parameters determine whether a reset is required to clear the alarm status.
When these parameters are 1, the alarm is latched ON when the alarm occurs.
After the alarm condition returns to normal, a reset is required to clear the alarm
status (for example, PCmd_Reset, OCmd_Reset, or Inp_Reset are required to
clear Alm_FailtoStart after the alarm is set and the value returns to normal).
When these parameters are 0, no reset is required and the alarm status is cleared
when the alarm condition returns to normal.
IMPORTANT:
If the reset clears the alarm, it also acknowledges the alarm.
Cfg_FailToStopResetReqd
FailToStop.Cfg_ResetReqd
Cfg_IntlkTripResetReqd
IntlkTrip.Cfg_ResetReqd
Cfg_DriveFaultResetReqd
DriveFault.Cfg_ResetReqd
Cfg_IOFaultResetReqd
IOFault.Cfg_ResetReqd
Cfg_FailToStartAckReqd
BOOL
FailToStart.Cfg_AckReqd
1
These parameters determine whether an acknowledgement is required for an
alarm. When these parameters are 1, the acknowledge (ack) bit is cleared when
the alarm occurs. An acknowledge command (for example,
PCmd_FailtoStartAck) is required to acknowledge the alarm. When set to 0, the
Acknowledge bit is set when an alarm occurs indicating an acknowledged alarm
and no acknowledge command is required.
Cfg_FailToStopAckReqd
FailToStop.Cfg_AckReqd
Cfg_IntlkTripAckReqd
IntlkTrip.Cfg_AckReqd
Cfg_DriveFaultAckReqd
DriveFault.Cfg_AckReqd
Cfg_IOFaultAckReqd
IOFault.Cfg_AckReqd
Cfg_FailToStartSeverity
INT
FailToStart.Cfg_Severity
1000
These parameters determine the severity of each alarm that gauges the color and
symbol that are used to indicate alarm status on the faceplate and global object.
The following are valid values:
1…250 = Low
251…500 = Medium
501…750 = High
751…1000 = Urgent
IMPORTANT:
These severity priorities drive only the indication on the global
object and faceplate. The Alarm and Events definition severity drives the color
and symbol that is used on the alarm banner and alarm summary as well as the
value returned by the FactoryTalk Alarm and Events software display commands.
Cfg_FailToStopSeverity
FailToStop.Cfg_Severity
1000
Cfg_IntlkTripSeverity
IntlkTrip.Cfg_Severity
500
Cfg_DriveFaultSeverity
DriveFault.Cfg_Severity
1000
Cfg_IOFaultSeverity
IOFault.Cfg_Severity
1000
Cfg_MinSpdRef
REAL
0.0
Minimum speed reference in engineering units (for limiting).
Cfg_MaxSpdRef
REAL
60.0
Maximum speed reference in engineering units (for limiting).
Cfg_SpeedRefRawMin
DINT
0
Speed reference minimum in drive (raw) units (for scaling).
Cfg_SpeedRefRawMax
DINT
60000
Speed reference maximum in drive (raw) units (for scaling).
Table 8 - P_PF7000 Drive Input Parameters
Input Parameter
Data
Type
Alias For
Default