PowerFlex Digital DC Drive User Manual -
Publication 20P-UM001C-EN-P - July 2008
Supplemental Drive Information
A-21
Table A.T 460V AC Input, Non-Regenerative Drives
DC Contactor Crimp Lug Kit
Specifications
Use the information provided in the table below to assist you in ordering the
correct Lug kit for your application.
Drive Cat. No.
DC
Amps
AC
Line
Amps
HP
Dynamic Brake
Resistor Kit Cat. No.
Armature
Voltage
(Volts)
DB Resistor
Size (ohms)
DB
Resistor
Size
(Watts)
Brake
Amps
Required
DC Loop
Contactor
Cat. No.
(4)
DC Contactor
Crimp Lugs Cat.
No.
(9)
20P-21AD4P1 4.1
3.3
2
1370-DBH63
500
81
255
6.17
1370-DC56
1370-LG40
20P-21AD6P0 6
4.9
3
1370-DBH64
500
62
245
8.06
1370-DC56
1370-LG40
20P-21AD010 10
8.2
5
1370-DBH65
500
45
245
11.11
1370-DC56
1370-LG40
20P-21AD014 14
11.4
7.5
1370-DBH66
500
27
350
18.52
1370-DC56
1370-LG40
20P-21AD019 19
15.5
10
1370-DBH67
500
20
420
25.00
1370-DC56
1370-LG40
20P-21AD027 27
22.1
15
1370-DBH68
500
12
405
41.67
1370-DC56
1370-LG40
20P-21AD035 35
28.6
20
1370-DBH69
500
5
330
100.00
1370-DC56
1370-LG40
20P-21AD045 45
36.8
25
1370-DBH70
500
4.5
330
111.11
1370-DC56
1370-LG52
20P-21AD052 52
42.5
30
1370-DBH71
500
3.5
385
142.86
1370-DC56
1370-LG52
20P-21AD073 73
59.6
40
1370-DBH72
500
2.6
345
192.31
1370-DC110 1370-LG92
20P-21AD086 86
70.3
50
1370-DBH73
500
2
345
250.00
1370-DC110 1370-LG92
20P-21AD100 100
81.7
60
1370-DBH74
500
2
345
250.00
1370-DC110 1370-LG110
20P-21AD129 129
105.4
75
1370-DBH75
500
1
270
500.00
1370-DC180 1370-LG140
20P-21AD167 167
136.4
100 1370-DBH76
500
0.7
280
714.29
1370-DC180 1370-LG180
20P-21AD207 207
169.1
125 1370-DBH77
500
0.7
280
714.29
1370-DC280 1370-LG228
20P-21AD250 250
204.3
150 1370-DBH78
500
0.5
365
1000.00
1370-DC280 1370-LG268
20P-21AD330 330
269.6
200 1370-DBH79
500
0.7
280
714.29
(5)
(10)
20P-21AD412 412
336.6
250
(1)
500
0.808
7292
–
(6)
(10)
20P-21AD495 495
404.4
300
(2)
500
0.595
6069
–
(7)
(10)
20P-21AD667 667
544.9
400
(3)
500
0.542
6439
–
(8)
(10)
(1)
HUBBELL_Y95W808GB - Must be sourced separately from drive.
(2)
HUBBELL_Y101W595GB - Must be sourced separately from drive.
(3)
HUBBELL_Y109W542GB - Must be sourced separately from drive.
(4)
Coil voltage = 115V AC, 50/60Hz.
(5)
ABB_EHDB360C-1L-22 - ABB Contactor for drives with a dynamic brake. Must be sourcing separately from drive.
(6)
ABB_EHDB520C2P-1L - ABB contactor for drives with no dynamic brake. ABB_EHDB520C-1L - ABB contactor for drives with a dynamic brake. Must be sourced separately from drive.
(7)
ABB_EHDB650C2P-1L - ABB contactor for drives with no dynamic brake. ABB_EHDB650C-1L - ABB contactor for drives with a dynamic brake. Must be sourced separately from drive.
(8)
ABB_EHDB800C2P-1L - ABB contactor for drives with no dynamic brake. ABB_EHDB800C-1L - ABB contactor for drives with a dynamic brake. Must be sourced separately from drive.
(9)
See
DC Contactor Crimp Lug Kit Specifications on page A-21
(10)
Wire and Lug size dependant on Cabinet dims and local codes.
Rated Motor
Armature Current
(1)
A DC
DC Contactor Rating
A DC
Armature Conductor
Size
(2)
AWG
DB Conductor Size
(3)
AWG
Armature Conductor
Crimp Lug Hole Size
DB Conductor Crimp
Lug Hole Size
Lug Kit Catalog
Number
4.1 - 35
56
8
8
#10
#10
1370-LG40
45 - 52
56
6
8
#10
#10
1370-LG52
55
56
4
8
#10
#10
1370-LG56
60 - 86
110
2
6
0.25 in.
0.25 in.
1370-LG92
100 - 110
110
1/0
4
0.25 in.
0.25 in.
1370-LG110
129
180
2/0
2
0.3125 in.
0.3125 in.
1370-LG140
146
180
3/0
2
0.3125 in.
0.3125 in.
1370-LG160
147 - 167
180
4/0
2
0.3125 in.
0.3125 in.
1370-LG180
207 - 218
280
300MCM
1/0
0.5 in.
0.375 in.
1370-LG228
250 - 265
280
400MCM
2/0
0.5 in.
0.375 in.
1370-LG268
(1)
The Rated Motor Armature Current is taken directly from the motor nameplate or motor data. The current listed in this column is the maximum current allowed for the Armature Conductor
Size (column 3) and the DC Contactor Rating (column 2).
(2)
The armature conductors are sized by multiplying the Rated Motor Armature Current by 1.25 as provided for in NEC 420-22 (1987). The DC lug ratings are determined from NEC Table 310-16
(1987) for copper conductors, insulation temperature rated at 75° C (167° F) at an ambient temperature of 30° C (86° F). If conditions are other than shown in NEC Table 310-16, then refer
to application codes.
(3)
The dynamic braking (DB) conductors are sized as in footnote 2 above, but at half ampacity due to the short time duration of current flow in these conductors, and has been sized to satisfy
NEMA Standard ICS 3-302.62 - Dynamic Braking. If the load inertia is larger than that of the motor, calculations must be made to determine correct conductor sizing and DB resistor wattage
per NEMA Standard ICS 3-302.62.
Содержание PowerFlex series
Страница 1: ...USER MANUAL Firmware Version 1 006 2 001 PowerFlex Digital DC Drive ...
Страница 190: ...PowerFlex Digital DC Drive User Manual Publication 20P UM001C EN P July 2008 A 22 Supplemental Drive Information Notes ...
Страница 292: ...Index 24 PowerFlex Digital DC Drive User Manual Publication 20P UM001C EN P July 2008 ...
Страница 293: ......