24
MicroLogix 1200 Programmable Controllers
Publication 1762-IN006C-EN-P - September 2009
Output Specifications
General
Relay Contact Ratings
Description
1762
-L24AWA
-L24BWA
-L24AWAR
-L24BWAR
-L24BXB
-L24BXBR
-L40AWA
-L40BWA
-L40AWAR
-L40BWAR
-L40BXB
-L40BXBR
Relay and FET Outputs
Maximum Controlled Load
1440 VA
Maximum Continuous Current:
Current per Group Common
8A
7.5A
8A
8A
Current per Controller
at 150V max
30A or total of per-point loads, whichever is less
at 240V max
20A or total of per-point loads, whichever is less
Relay Outputs
Turn On Time/Turn Off Time
10 msec (minimum)
(1)
(1)
scan time dependent
Load Current
10 mA (minimum)
Maximum Volts
Amperes
Amperes
Continuous
Volt-Amperes
Make
Break
Make
Break
240V ac
7.5A
0.75A
2.5A
(2)
(2)
1.5A above 40°C.
1800 VA
180 VA
120V ac
15A
1.5A
2.5A
(2)
1800 VA
180 VA
125V dc
0.22A
(1)
(1)
For dc voltage applications, the make/break ampere rating for relay contacts can be determined by dividing 28 VA by the
applied dc voltage. For example, 28 VA/48V dc = 0.58A. For dc voltage applications less than 14V, the make/break ratings
for relay contacts cannot exceed 2A.
1.0A
28 VA
24V dc
1.2A
(1)
2.0A