Working Voltage
Turn-On Time (maximum)
0.1 msec
6 μsec
Turn-Off Time (maximum)
1.0 msec
18 μsec
Repeatability (maximum)
n/a
2 μsec
Drift (maximum)
n/a
1 μsec per 5°C (9°F)
(1)
Output 2 is designed to provide increased functionality over the other FET outputs. Output 2 may be used like the other FET
transistor outputs, but in addition, within a limited current range, it may be operated at a higher speed. Output 2 also
provides a pulse train output (PTO) or pulse width modulation output (PWM) function.
Description
1762-L24AWA, 1762-L40AWA, 1762-L24AWAR, 1762-L40AWAR
Power Supply Input to
Backplane Isolation
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (IEC Class 2 reinforced insulation)
Input Group to Backplane
Isolation
Verified by one of the following dielectric tests:1517V ac for 1 second or 2145V
dc for 1 second
132V ac Working Voltage (IEC Class 2 reinforced insulation)
Input Group to Input Group
Isolation
Verified by one of the following dielectric tests:1517V ac for 1 second or 2145V
dc for 1 second
132V ac Working Voltage (basic insulation)
Output Group to Backplane
Isolation
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1 second
265V ac Working Voltage (IEC Class 2 reinforced insulation)
Output Group to Output
Group Isolation
Verified by one of the following dielectric tests: 1836V ac for 1 second or
2596V dc for 1second
265V ac Working Voltage (basic insulation) 150V ac Working Voltage (IEC Class
2 reinforced insulation).