Note: You can also select/highlight multiple parameters then click the Add - > button. This makes adding parameters go a
lot faster.
14.
Add the following parameters:
Parameter 30 - Language
Parameter 43 - Minimum Freq
Parameter 31 - Motor NP Volts
Parameter 44 - Maximum Freq
Parameter 32 - Motor NP Hertz
Parameter 45 - Stop Mode
Parameter 33 - Motor OL Current
Parameter 46 - Start Source 1
Parameter 34 - Motor NP FLA
Parameter 47 - Speed Reference1
Parameter 35 - Motor NP Poles
Parameter 62 - DigIn TermBlk 02
Parameter 36 - Motor NP RPM
Parameter 63 - DigIn TermBlk 03
Parameter 37 - Motor NP Power
Parameter 64 - 2-Wire Mode
Parameter 39 - Torque Perf Mode
Parameter 65 - DigIn TermBlk 05
Parameter 40 - Autotune
Parameter 76 - Relay Out1 Sel
Parameter 41 - Accel Time 1
Parameter 81 - Relay Out2 Sel
Parameter 42 - Decel Time 1
Once the parameters have been added Click OK to download this custom group to the drive.
Page
30
of
64