LDAT-Series Integrated Linear Thrusters
Rockwell Automation Publication LDAT-IN001B-EN-P - March 2020
Home
Follow these steps to home the linear thruster.
1.
From the Workspace, select Mode Configuration>Homing.
2.
Set the parameters to the following values.
If linear thruster does not move to negative spring stop during homing it may be
necessary to increase the Home Current Value.
3.
From the Workspace, select Indexing.
4.
Set the parameter Auto Start Index to Off.
5.
Click Indexing Control Panel.
6.
Click Enable Drive.
7.
Click Start Homing.
The linear thruster moves to the negative spring stop and returns to the home position.
The In Position and At Home display indicators turn yellow.
Parameter
Value
Home Type
Home to Current Value/Back to Marker
Auto Start Homing on Enable
Inactive
Home Sensor Back-off
Inactive
Homing Velocity
-0.0100 m/s
Homing Accel/Decel
1.0000 m/s/s
Offset Move Distance
2000.0000 counts
Stop Home Decel
1.0000 m/s/s
Home Sensor Polarity
Active Going Transition
Home Position
0.000 counts
Creep Velocity
0.0100 m/s
Home Current Value
2.0000 Amps