Rockwell Automation Publication 440R-IN089A-EN-P - July 2022

Minotaur MSR142RTP Monitoring Safety Relay Installation Instructions

Diagnostics

The solid-state status signal Y35 indicates the safety input state. The solid-state 
status output Y32 and the auxiliary (N.C.) output 41-42 signals the safety output 
state.

Safety Input

One safety device can be monitored per unit. According to the wiring inputs, 
cross-loop monitoring of the inputs is enabled or disabled. You can enable 
cross-loop monitoring for 2-channel safety inputs in 4-wire connection (S11-S12, 
S21-S22). Cross-loop monitoring is disabled for single-channel inputs, dual-channel 
inputs in 3-wire connection, and 24V DC signals. For external 24V DC signals, the 
negative pole must connect to S21.

Reset

Reset modes - The reset mode is configurable for automatic/manual start 
and manual monitored reset (MSR

xxx

RT). 

A valid start/reset can only operate if the feedback circuit is closed. 
Feedback contacts (N.C.) of controlled actuators connect to Y1-Y2. 

T - Automatic/manual start 

(a)

In Automatic/Manual Start mode, the reset circuit S33-S34 is not 
monitored against signal changes (no edge detection). The safety relay is 
active once the safety inputs and the reset circuit close. If the safety 
inputs and reset circuit concurrently close during power-up, the safety 
relay activates immediately.

R - Manual monitored reset 

(b)

In Manual Monitored Reset mode, a signal change of the reset circuit 
(S33-S34) is required and monitored. A reset fault occurs if the safety 
inputs remain open while the reset circuit is closed.

-

Positive edge:

The safety relay is active once the safety inputs close and then the 
reset circuit is closed.

-

Negative edge (440R-

xxxxx

M):

The safety relay is active once the safety inputs close and then the 
reset circuit closes and releases again. The circuit resets upon release 
of the Reset button.

For both methods, the MSR142RTP safety relay is suitable for the safety 
requirements according to EN/ISO 13849-1.

Response time

15 ms

Recovery time

100 ms

Impulse withstand voltage

2500V (external wiring according to rated voltage)

Pollution degree

2

Installation group

Overvoltage category III, VDE 0110-1

Operating temperature

-5…+55 °C (23…131 °F)

Relative Humidity

90% 

Enclosure protection

IP40 (NEMA 1)

Terminal protection

IP20

Wiring

Use copper that withstands 60/75 °C (140/167 °F)

Conductor size

0.2...2.5 mm

2

 (24…12 AWG)

Torque settings

Terminal screws: 0.6…0.8 N•m (5…7 lb•in)

Case material

Polyamide PA 6.6

Mounting

35 mm (1.38 in.) DIN rail in enclosure to a minimum of IP54

Weight

24V AC/DC: 470 g (1.04 lb)
115V AC or 230V AC: 607 g (1.34 lb)

Vibration

10…55 Hz, 0.35 mm (0.01 in.)

(1)

Operation time (day, hour)

(2)

Cycle time (hour, sec)

Max PLc: 1-CH 

(1)

; N.C.

(1)

1-CH = Single-channel

Max PLd: 2-CH 

(2)

; 3-wire connection

Max PLe: 2-CH 

(2)

; 24V DC signal

Max PLe: 2-CH 

(2)

; 4-wire connection, cross 

faults require fault reset

Table 1 - Technical Specifications  (Continued)

Attribute

Value

(2)

2-CH = Dual-channel

(a)

T = Jumper X1-X2, X3-X4

(b)

R = No jumper

X3

X1

Y1

X4

X2

Y2 S34

S33

K2

K1

S12

S11

X3

X1

Y1

X4

X2

Y2 S34

S33

K2

K1

S12

S11

MSR

xxx

T

MSR

xxx

T

440R-

xxxxx

M

S12

X3

X1

Y1

X4

X2

Y2 S34

S33

K2

K1

S11

S12

X3

X1

Y1

X4

X2

Y2 S34

S33

K2

K1

S11

MSR

xxx

R

MSR

xxx

R

440R-

xxxxx

M

MSR

xxx

R

440R-

xxxxx

M

Содержание Allen-Bradley Guardmaster Minotaur MSR142RTP

Страница 1: ...nction or damage is present do not attempt to repair Replaced the unit before machine operation is allowed Do not dismantle the unit IMPORTANT The safety inputs of these products are described as normally closed N C that is with the guard closed the actuator in place where relevant and the machine able to start You must prevent exposure to shock and or vibration in excess of those specifications i...

Страница 2: ... safety inputs remain open while the reset circuit is closed Positive edge The safety relay is active once the safety inputs close and then the reset circuit is closed Negative edge 440R xxxxxM The safety relay is active once the safety inputs close and then the reset circuit closes and releases again The circuit resets upon release of the Reset button For both methods the MSR142RTP safety relay i...

Страница 3: ...tput Active Inputs Closed Table 2 Circuit Diagram Explanation Abbreviation Description A1 A2 Power S11 S12 S21 S22 Safety input N C X1 X2 X3 X4 S33 S34 Link for auto reset Y1 Y2 Monitoring loop feedback 13 14 43 44 Safety output 1 N O 23 24 53 54 Safety output 2 N O 33 34 63 64 73 74 Safety output 3 N O 81 82 101 102 Auxiliary output CH1 N C 91 92 111 112 Auxiliary output CH2 N C Y31 Y32 Y35 Auxil...

Страница 4: ... the MSR142RTP safety relay in safety circuits according to DIN EN 60204 1 VDE 0113 part 1 Safety requirements that are specified in Specifications on page 1 are maximum based on the operation mode and wiring Specifications are applicable only if the safety function is demanded at least once within 6 months All diagnostic tests are conducted at least before next demand The mission time TM for the ...

Отзывы: