12
Rockwell Automation Publication 1715-RM001A-EN-P - June 2019
Chapter 1
The ControlLogix/1715 SIL 2 System
• Only 1756-L7x controllers are supported
EtherNet/IP communication cards
• Use of a 1756-EN2TR or 1756-EN2TRXT is required to achieve SIL 2 in
the application
• Other EtherNet/IP communication modules (1756-ENBT, 1756-EN2T,
1756-EN2TXT) can be used for non-safety loop communication
• 1715 IO only communicates via EtherNet/IP so no ControlNet modules
are listed here.
Figure 3 - Redundancy System Configuration Example