background image

18

Rockwell Automation Publication 1715-RM001A-EN-P - June 2019

Chapter 2

Features of the ControlLogix SIL 2 System

To perform program verification, follow these steps in RSLogix 5000 software or 

the Studio 5000 Logix Designer application.

1.

With the programming software closed rename the project.

2.

Start the programming software, upload the controller project, and save it.

3.

Open the compare tool and select both files.

4.

Start the compare operation.

5.

Review the compare output results and verify that everything matches 

without error. (Project documentation differences can exist.)

6.

Save the compare results as part of the verification process.

7.

Delete the upload file.

8.

To maintain project documentation, rename the original project file 

(change back) to the original project name.

HMI Precautions

You must exercise precautions and implement specific techniques on HMI 

devices. These precautions include, but are not limited to the following:

• Limited access and security
• Specifications, testing, and validation
• Restrictions on data and access
• Limits on data and parameters

HMI- related functions consist of two primary activities: reading and writing 

data.

Reading Data

Reading data is unrestricted because reading doesn't affect the operation or 

behavior of the safety system. However, the number, frequency, and size of the 

data being read can affect controller performance. To avoid safety-related 

nuisance trips, use good communication practices to limit the impact of 

communication processing on the controller. Do not set read rates to the fastest 

rate possible.

IMPORTANT

Do not use memory cards to transfer the safety application automatically.

The AutoFlash firmware feature is not supported for SIL 2 safety applications.

Содержание Allen-Bradley ControlLogix SIL 2

Страница 1: ...Using ControlLogix SIL 2 with 1715 I O Catalog Numbers ControlLogix 5570 1715 AENTR 1715 IB16D 1715 IF16 1715 OB8DE 1715 OF8I Reference Manual OriginalInstructions...

Страница 2: ...nformation circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written permission of Rockwell Automation Inc is prohibited T...

Страница 3: ...gurations 14 Application Development Requirements 15 Security 15 Safety SIL Task 16 Setting the SIL2 Task Period Configuration 17 Forcing 17 Verify Download 17 HMI Precautions 18 Reading Data 18 Writi...

Страница 4: ...4 Rockwell Automation Publication 1715 RM001A EN P June 2019 Table of Contents Notes...

Страница 5: ...You must follow your own local laws and regulations and refer to your own local or supplied system safety manual installation and operator maintenance manuals Ultimately you are responsible to apply...

Страница 6: ...systems There is usually some confusion between GuardLogix and ControlLogix SIL 2 since GuardLogix can be used in a SIL 2 system and it is based on ControlLogix In this guide we refer to ControlLogix...

Страница 7: ...esigned to operate in a safety system there is no longer any need for special wiring or IFMs to use ControlLogix in a SIL 2 manner Either or Both the I O system or controller system can be simplex or...

Страница 8: ...ll SIL 2 capable since 1756 ControlLogix is capable of running SIL 2 with one controller or 1715 I O module It is up to the user if they want to continue running in this state ControlLogix Redundancy...

Страница 9: ...If there is a redundancy switch over it is always recommended to investigate why it switched over IMPORTANT When programming your redundant system program so your redundancy system status is continuou...

Страница 10: ...producer Unicast I O is not supported in a redundancy system If you attempt to use consumed Unicast connections disqualification occurs and qualification of an unsynchronized redundant chassis pair i...

Страница 11: ...nd settings based on a simplex system and then make it redundant You should never communicate with the controller in the secondary chassis other than to obtain diagnostics RedundancySystemDetails Two...

Страница 12: ...IP communication cards Use of a 1756 EN2TR or 1756 EN2TRXT is required to achieve SIL 2 in the application Other EtherNet IP communication modules 1756 ENBT 1756 EN2T 1756 EN2TXT can be used for non s...

Страница 13: ...Run No online changes are possible Program This stops the execution of the application code and allow online changes Remote This software enabled mode can be Program or Run In this mode you can make o...

Страница 14: ...ese SIL 2 architectures are for fail safe low and high demand applications All SIL 2 architectures can be used for de energize to trip applications With special precautions CLX 1715 SIL 2 can be used...

Страница 15: ...actices A test plan is documented and adhered to including well understood proof test requirements and procedures A well designed validation process is defined and implemented A well designed Manageme...

Страница 16: ...y controller for things like determining the status of the redundancy system or diagnostics does not violate the above statement since there are no BPCS Basic Process Control System control elements p...

Страница 17: ...receives packets with this inconsistency and discard the data From the controller you will notice SIL 2 Reset Needed on both the AOI and AOP The ability to manually control 1715 inputs and outputs wou...

Страница 18: ...iginal project name HMI Precautions You must exercise precautions and implement specific techniques on HMI devices These precautions include but are not limited to the following Limited access and sec...

Страница 19: ...he following sequence of events occurs 1 The new variable must be sent twice to two different tags that is both values must not be written to with one command 2 Safety related code that executes in th...

Страница 20: ...20 Rockwell Automation Publication 1715 RM001A EN P June 2019 Chapter 2 Features of the ControlLogix SIL 2 System Notes...

Страница 21: ...o cross wiring of outputs to inputs is needed any longer nor is the requirement to have two separate I O chassis for Fault Tolerance For hardware selection refer Chapter 6 of Redundant I O System User...

Страница 22: ...lication 1715 RM001A EN P June 2019 Chapter 3 Using the 1715 I O Figure 6 Typical Duplex Configuration IMPORTANT For duplex configurations a SIL 2 fault tolerant architecture has dual input dual adapt...

Страница 23: ...e modular architecture lets you build and adapt a system to suit the specific needs of an installation The architecture lets you choose from different levels of I O fault tolerance Any of the modules...

Страница 24: ...only to form the backplane for the system Termination assemblies are available in Simplex and Duplex configuration They mount onto the 1715 A3IO I O module base unit and connect the I O modules to th...

Страница 25: ...1715 RM001A EN P June 2019 25 Using the 1715 I O Chapter 3 1715 AENTRAdapterRedundantPair The 1715 adapter communicates via the EtherNet IP network using CIP protocol to a 1756 ControlLogix controlle...

Страница 26: ...01A EN P June 2019 Chapter 3 Using the 1715 I O 1715 A2AAdapterBaseUnit The adapter base unit holds a pair of adapters It also contains connectors for power 2 and network connections 4 The network con...

Страница 27: ...next to a duplex pair There is no need to leave a space empty 1715DigitalandAnalogI Omodules Your system can be configured with any combination of I O modules and in either Simplex or Duplex mode The...

Страница 28: ...duplex TA that provides fault tolerant operation for eight digital output channels and mates with redundant 1715 OB8DE digital output modules A 1715 TADIF16 16 channel duplex TA that provides terminat...

Страница 29: ...mounted and connections are chained together from left to right Figure 8 Module Placement Description Item Description 1 Adapter base unit 2 Adapter A module 3 Adapter B module 4 I O base unit 5 Simp...

Страница 30: ...30 Rockwell Automation Publication 1715 RM001A EN P June 2019 Chapter 3 Using the 1715 I O Notes...

Страница 31: ...using 1715 and ControlLogix SIL 2 IMPORTANT TheT VRheinlandGrouphasapprovedthe1715RedundantI OSystemforuse in safety related applications up to and including SIL 2 according to these standards IEC 61...

Страница 32: ...vailability but doesn t add to the safety capability Ethernet The Ethernet architecture has no effect on SIL 2 safety functions You can use any appropriate Ethernet network for your application From a...

Страница 33: ...state values The module enters a Shutdown mode when the time between controller communications exceeds the CRTL If a module fails then all of its channels are set to the de energized state Output mod...

Страница 34: ...etermines how long the connection can operate with old data before going to its configured safe state For an input module if the CRTL expires before the Add On Instruction detects valid data the value...

Страница 35: ...tasks to complete Even if you do not use any other tasks there are still other internal tasks running like communications In other words if the SIL 2 periodic task is set too low it is possible to us...

Страница 36: ...that a duplex module only requires one Add On Instruction 1715 SIL 2 Add On Instructions must be imported into the RSLogix 5000 project Import only the Add On Instructions you need based on your SIL...

Страница 37: ...n Instructions you do not read inputs directly from the input table nor do you write directly to the output tags You read inputs from an Add On Instruction tag that is called reconciled input data and...

Страница 38: ...38 Rockwell Automation Publication 1715 RM001A EN P June 2019 Chapter 4 Using1715 Hardware in a ControlLogix SIL 2 System...

Страница 39: ...a ControlLogix SIL 2 System Chapter 4 InputDataSystem Input modules send data only one way from the input module to the controller OutputDataSystem Output modules send data both ways Status is sent fr...

Страница 40: ...s must be fitted with external line and load integrity monitoring and safety critical read back of the line status signals Any line or load failure must trigger an alarm See 1715 UM001 for more inform...

Страница 41: ......

Страница 42: ...ourcalldirectlytoatechnicalsupport engineer http www rockwellautomation com global support direct dial page Literature Library Installation Instructions Manuals Brochures and Technical Data http www r...

Отзывы: