118
Rockwell Automation Publication 5069-UM003B-EN-P - January 2020
Appendix A
Module Tags
I
xx
.Fault
BOOL
Indicates that channel data is inaccurate and cannot be trusted for
use in the application.
• 0 = Good
• 1 = Bad, causing fault
If the tag is set to 1, you must troubleshoot the
module to correct the cause of the inaccuracy.
IMPORTANT
: Once the condition that causes the
tag to change to 1 is removed, the tag
automatically resets to 0.
I
xx
.Uncertain
BOOL
Indicates that the channel data can be inaccurate but the degree of
inaccuracy is not known.
• 0 = Good data
• 1 = Uncertain data
If the tag is set to 1, you must troubleshoot the
module to correct the cause of the inaccuracy.
IMPORTANT
: Once the condition that causes the
tag to change to 1 is removed, the tag
automatically resets to 0.
I
xx
.LastExecutedCommand
SINT
Indicates the number of the latest executed command, and the
Update Counter indicates the status for command level. If this value
is updated, either a new command is executed, not changed,
command is not executed, or have not finished yet.
• -1(value shown before any command)
• 0…49
I
xx
.Command
yy
.Fault
BOOL
Indicates that channel data is inaccurate and cannot be trusted for
use in the application.
The number of Commandyy tags (where yy can be 0…49) are
dynamically created depending on the command list you create.
• 0 = Good
• 1 = Bad, causing fault
If the tag is set to 1, you must troubleshoot the
module to correct the cause of the inaccuracy.
IMPORTANT
: Once the condition that causes the
tag to change to 1 is removed, the tag
automatically resets to 0.
I
xx
.Command
yy
.Uncertain
BOOL
Indicates that the channel data can be inaccurate but the degree of
inaccuracy is not known.
• 0 = Good data
• 1 = Uncertain data
If the tag is set to 1, you must troubleshoot the
module to correct the cause of the inaccuracy.
IMPORTANT
: Once the condition that causes the
tag to change to 1 is removed, the tag
automatically resets to 0.
I
xx
.Command
yy
.Disabled
BOOL
Status whether the Modbus Command is disabled and not executed
on every scan of the module.
• 0 = Enabled
• 1 = Disabled
I
xx
.Command
yy
.ParityError
BOOL
Status that shows whether a parity error has occurred or not.
• 0 = Non-occurrence
• 1 = Occurrence
I
xx
.Command
yy
.ResponseTimeout
BOOL
Shows if there was a response timeout.
• 0 = Non-occurrence
• 1 = Occurrence
I
xx
.Command
yy
.FramingError
BOOL
Shows if there was a framing error.
• 0 = Non-occurrence
• 1 = Occurrence
I
xx
.Command
yy
.BufferOverrun
BOOL
Shows if a buffer overrun has occurred.
• 0 = Non-occurrence
• 1 = Occurrence
I
xx
.Commandy
y
.SlaveErrorCode
SINT
Indicates if a slave error code has occurred.
•
IMPORTANT:
A slave error code is not equal to an exception
code.
• 0 = Non-occurrence
• 1 = Occurrence
I
xx
.Command
yy
.ExecutionCount
SINT
The number of times the command is executed.
• -128...127
Ixx.Commandxx.Datazzzzzz
SINT, INT, or
REAL
Command read response data.
The data for this tag is dynamic according to how the command list
is created.
• -128…+127
• -32768…+32767
Table 28 - Modbus Master Input Tags
Name
Data Type
Definition
Valid Values
Содержание Allen-Bradley 5069-L3100ERMS2
Страница 1: ...Compact 5000 I O Serial Module Catalog Numbers 5069 SERIAL User Manual OriginalInstructions ...
Страница 130: ...130 Rockwell Automation Publication 5069 UM003B EN P January 2020 Appendix A ModuleTags Notes ...
Страница 143: ...Rockwell Automation Publication 5069 UM003B EN P January 2020 143 Programming Example Appendix C ...
Страница 146: ...146 Rockwell Automation Publication 5069 UM003B EN P January 2020 Appendix C Programming Example ...
Страница 155: ......