Rockwell Automation Publication 5069-UM003B-EN-P - January 2020
87
Compact 5000 I/O Serial Module Configuration
Chapter 4
Data Index
This value indicates the offset of the register type address in controller tags that
allow the serial module to read or write required data to or from the controller.
Each register type has a predefined array size that can be used for the Modbus
Slave as indicated in the
Modbus Slave Address Table Limits
. For example, a
Holding register has the limit of 100 INT. The array size is 0…99 and the Data
index is 0…99 when the Holding register is used depending on the size and the
location where you want to store the information.
If you exceed the data limit, an error can occur. This error would appear as
in
Figure 28
.
Figure 28 - Data Index Error
Table 23 - Modbus Slave Module Definition Parameters
Parameter
Definition
Register Type
• Disabled (default)
• Coils
• Discrete Inputs
• Input Registers
• Holding Registers
Data Type
• BOOL
• INT
• REAL
Register Start Address
• 0…65535
(default = 0)
Register Length
• Dependent on Data Type
– BOOL: 1…128
(default =1)
– INT: 1…100
(default = 1)
– REAL: 1…50
(default = 1)
Data Index
Location of data in the output or input tags depending on the register type defined.
For more information, see the following section on
.
Содержание Allen-Bradley 5069-L3100ERMS2
Страница 1: ...Compact 5000 I O Serial Module Catalog Numbers 5069 SERIAL User Manual OriginalInstructions ...
Страница 130: ...130 Rockwell Automation Publication 5069 UM003B EN P January 2020 Appendix A ModuleTags Notes ...
Страница 143: ...Rockwell Automation Publication 5069 UM003B EN P January 2020 143 Programming Example Appendix C ...
Страница 146: ...146 Rockwell Automation Publication 5069 UM003B EN P January 2020 Appendix C Programming Example ...
Страница 155: ......