Compact 5000 I/O Serial Module Configuration
Chapter 4
Master Command List Limitations
• A maximum of 50 commands can be created. The commands are subject
to available connection memory.
• Each Modbus Master supports up to two data connections.
• The First Data Connection supports a max of 464 bytes of read data and
476 bytes of write data. The Second Data Connection supports a max of
472 bytes of read data and 488 bytes of write data.
• Each command can have a max of either 125 words read or 123 words
write or 2000 coil/discrete input read or 1968 coils written.
• Each Read command uses:
– Four bytes of input data for command status
– Two bytes of input data per holding register or input register read.
– One byte of input data per every 1…8 coils or discrete inputs read.
– Padding to align command to 4 bytes.
• Each Write command uses:
– Four bytes of input data for command status
– Two bytes of output data per holding register written.
– One byte of output data per every 1…8 coils written.
– Padding to align command to 4 bytes.
• Remaining available data is displayed.
• An error message appears when connection memory is exceeded.
Master Command Memory Usage
Input and output data size is available in the Add-On Profile.
• View data size to verify data has not exceeded data available per channel:
Содержание Allen-Bradley 5069-L3100ERMS2
Страница 1: ...Compact 5000 I O Serial Module Catalog Numbers 5069 SERIAL User Manual OriginalInstructions ...
Страница 130: ...130 Rockwell Automation Publication 5069 UM003B EN P January 2020 Appendix A ModuleTags Notes ...
Страница 143: ...Rockwell Automation Publication 5069 UM003B EN P January 2020 143 Programming Example Appendix C ...
Страница 146: ...146 Rockwell Automation Publication 5069 UM003B EN P January 2020 Appendix C Programming Example ...
Страница 155: ......