Appendix A Install, Wire, and Configure PROFIBUS Modules
Figure 22 - PROFIBUS Connector Wiring
Connect Power to the Block
To apply power to the block, see
Connect I/O Wiring
Consider the following guidelines when wiring your system:
General Guidelines
•
All module commons (ANLG COM) are connected in the analog
module.
The analog common (ANLG COM) is not connected to earth ground
inside the module.
•
Channels are not isolated from each other.
•
Do not use the analog module’s NC terminals as connection points.
•
To ensure optimum accuracy, limit overall cable impedance by keeping
your cable as short as possible. Locate the I/O system as close to your
sensors or actuators as your application permits.
•
Use Belden 8761, or equivalent, shielded wire.
•
Keep shield connection to ground as short as possible.
•
Under normal conditions, the drain wire and shield junction must be
connected to earth ground via a panel or DIN rail mounting screw at the
analog I/O module end.
Guidelines for Input Modules
•
If multiple power supplies are used with analog inputs, the power supply
commons must be connected together.
•
The module does not provide loop power for analog inputs. Use a power
supply that matches the input transmitter specifications.
Green — GND
Black — COM
Red — +24V DC
PROFIBUS
connector
Содержание Allen-Bradley 1790D-N0C2
Страница 6: ...6 Rockwell Automation Publication 1790 UM001B EN P April 2021 Table of Contents Notes ...
Страница 8: ...8 Rockwell Automation Publication 1790 UM001B EN P April 2021 Notes ...
Страница 24: ...24 Rockwell Automation Publication 1790 UM001B EN P April 2021 Chapter 2 Installation and Wiring Notes ...
Страница 62: ...62 Rockwell Automation Publication 1790 UM001B EN P April 2021 Index Notes ...
Страница 63: ...Rockwell Automation Publication 1790 UM001B EN P April 2021 63 CompactBlock LDX I O Analog Modules User Manual ...