44
Rockwell Automation Publication 1790-UM001B-EN-P - April 2021
Chapter 5 Module Diagnostics and Troubleshooting
Module Errors
lists possible errors that cause the analog input module status bits to
be set.
Channel Status Indicator
Operation
show individual channel status indicator operation.
Table 35 - Word/Bit Descriptions
Word
Decimal Bit
Description
Read Word 4
Bits 00…03
Status bits for individual channels — Bit 00 corresponds to input channel 0, bit
01 corresponds to input channel 1 and so on.
When set (1) indicates:
• No field power
• Open wire —
4…20 mA current input only
• Under range —
4…20 mA current input only
• Recoverable module fault (whole channel to be set)
• Unrecoverable module fault (whole channel to be set)
Bits 04…15
Not used: Set to 0
Table 36 - Status Bit Table 1790D-N4CO/-TN4CO, 1790D-TN4VO
Range Setting
Underrange
In Range
Overrange
Open Circuit
Short Circuit
No Field Power
4…20 mA
<4 mA
Set
Not set
>20 mA
Not set
Set
Set
Set
0…20 mA
<0 mA
Not set
Not set
>20 mA
Not set
Not set
Not set
Set
0…10V DC
<0V DC
Not set
Not set
>10V
Not set
Not set
Not set
Set
Table 37 - Analog Input Modules — 1790D-TN4C0
Status
Description
Flashing green/red
Power up
Off
Offline
Red
Online and no field power
Red
DeviceNet connection and no field power
Flashing red
(1)
(1) Green for 0…20 mA range.
Field power and open wire —
4…20 mA range only
(2)
(2) Can be determined from the data table.
Green
Field power and valid input
Green
Input over range
Flashing red
1
Input under range
<3 mA —
4…20 mA range only
2
Flashing red
Recoverable fault
Table 38 - Analog Output Modules — 1790D-TN0V2, 1790D-TN0C2
Status
Description
Flashing green/red
Power up
Off
Off line
Off
On line and no field power
Green
DeviceNet connection and no field power
Green
Field power and open wire
Green
Field power and valid output
Flashing red
Field power and output out of range
Flashing green
Output idle
Flashing red
Recoverable fault
Содержание Allen-Bradley 1790D-N0C2
Страница 6: ...6 Rockwell Automation Publication 1790 UM001B EN P April 2021 Table of Contents Notes ...
Страница 8: ...8 Rockwell Automation Publication 1790 UM001B EN P April 2021 Notes ...
Страница 24: ...24 Rockwell Automation Publication 1790 UM001B EN P April 2021 Chapter 2 Installation and Wiring Notes ...
Страница 62: ...62 Rockwell Automation Publication 1790 UM001B EN P April 2021 Index Notes ...
Страница 63: ...Rockwell Automation Publication 1790 UM001B EN P April 2021 63 CompactBlock LDX I O Analog Modules User Manual ...