Rockwell Automation Publication 1790-UM001B-EN-P - April 2021
13
Chapter
2
Installation and Wiring
This chapter tells you how to:
•
determine the power requirements for the modules
•
avoid electrostatic damage
•
install the module
•
wire the module’s terminal block
•
wire input devices
•
wire output devices
Power Requirements
The modules receive power through the DeviceNet network and from an
auxiliary 24V DC field supply.
shows the maximum power that the
modules draw.
General Considerations
Reduce Noise
Most applications require installation in an industrial enclosure to reduce the
effects of electrical interference. Analog inputs and outputs are highly
susceptible to electrical noise. Electrical noise coupled to the analog inputs
reduces the performance (accuracy) of the module.
Group your modules in the enclosure to minimize adverse effects from
radiated electrical noise and heat. Consider the following conditions when
selecting a location for the analog module. Position the module:
•
away from sources of electrical noise such as hard-contact switches,
relays, and AC motor drives
•
away from modules that generate significant radiated heat.
In addition, route shielded, twisted-pair analog input and output wiring away
from any high-voltage I/O wiring.
Table 2 - CompactBlock LDX I/O Module Power Requirements
Voltage Range
Power
DeviceNet Power
11…28.8 V DC
1.2 W @ 28.8V DC
Auxiliary 24V DC Field Power
21.6…26.4V DC
1.5 W @ 26.4V DC
Содержание Allen-Bradley 1790D-N0C2
Страница 6: ...6 Rockwell Automation Publication 1790 UM001B EN P April 2021 Table of Contents Notes ...
Страница 8: ...8 Rockwell Automation Publication 1790 UM001B EN P April 2021 Notes ...
Страница 24: ...24 Rockwell Automation Publication 1790 UM001B EN P April 2021 Chapter 2 Installation and Wiring Notes ...
Страница 62: ...62 Rockwell Automation Publication 1790 UM001B EN P April 2021 Index Notes ...
Страница 63: ...Rockwell Automation Publication 1790 UM001B EN P April 2021 63 CompactBlock LDX I O Analog Modules User Manual ...