Rockwell Automation Allen-Bradley 1606-XLB90E Скачать руководство пользователя страница 20

20

Rockwell Automation Publication 1606-RM121A-EN-P - October 2020

           

Series Operation

Devices of the same type can be connected in series for higher output voltages. 
It is possible to connect as many units in series as needed, providing the sum 
of the output voltage does not exceed 150V DC. Voltages with a potential above 
60V DC must be installed with a protection against touching.

Avoid return voltage (for example, from a decelerating motor or battery) which 
is applied to the output terminals.

Keep an installation clearance of 15 mm (0.59 in.) (left / right) between two 
power supplies and avoid installing the power supplies on top of each other. 
Do not use power supplies in series in mounting orientations other than the 
standard mounting orientation.

Leakage current, EMI, inrush current, and harmonics increase when using 
multiple devices.

Figure 26 - Series Operation

Parallel Use for 1+1 
Redundancy

Devices can be paralleled for 1+1 redundancy to gain higher system availability. 
Redundant systems require a certain amount of extra power to support the 
load in case one device fails. The simplest way is to put two devices in parallel. 
This is called a 1+1 redundancy. In case one device fails, the other one is 
automatically able to support the load current without any interruption. It is 
essential to use a redundancy module to decouple devices from each other. 
This helps prevent the defective unit from becoming a load for the other 
device, which helps to ensure that the output voltage can be maintained.

A means to report a defective or non-functional power supply is essential for 
redundant systems. This power supply does not incorporate such means of 
reporting. So if you use it for 1+1 redundancy, use it with a redundancy module 
that monitors and reports insufficient input voltage.

Alternatively, you could use another model of power supply that has a DC OK 
signal included. With a DC OK signal, you would not need the redundancy 
module to have the monitoring and reporting feature.

Unit A

Input

Output

Unit B

-

+

-

+

Load

+

-

Input

Output

Содержание Allen-Bradley 1606-XLB90E

Страница 1: ...DC Power Supply 24V 3 8 A 90 W Single phase Input Catalog Number 1606 XLB90E Reference Manual Original Instructions...

Страница 2: ...y Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written per...

Страница 3: ...Terminals 13 Lifetime Expectancy 13 Mean Time Between Failure 13 Electromagnetic Compatibility 14 Environment 15 Safety and Protection Features 16 Dielectric Strength 16 Approvals 17 Other Fulfilled...

Страница 4: ...4 Rockwell Automation Publication 1606 RM121A EN P October 2020 Notes...

Страница 5: ...compromising quality or reliability Width only 36 mm 1 42 in Efficiency up to 93 8 Low no load power losses Full power between 10 60 C 14 140 F Large screw terminals Terms Descriptions PE The abbrevia...

Страница 6: ...0 158 F Input voltage AC AC 100 240V 10 Mains frequency 50 60 Hz 6 Input current AC 1 45 A 0 95 A At 120 230V AC Power factor 0 58 0 45 At 120 230V AC Input inrush current 18 A peak 40 A peak At 120 2...

Страница 7: ...aker Attributes Values Notes AC 100V AC 120V AC 230V Input current Typ 1 69 A 1 45 A 0 95 A At 24V 3 8 A see Figure 3 Power factor Typ 0 6 0 58 0 45 At 24V 3 8 A see Figure 4 Start up delay Typ 50 ms...

Страница 8: ...ld start Typ 14 Apeak 18 Apeak 40 Apeak At 40 C 104 F ambient cold start Max 15 Apeak 20 Apeak 43 Apeak At 25 C 77 F ambient cold start Typ 12 Apeak 16 Apeak 35 Apeak At 25 C 77 F ambient cold start I...

Страница 9: ...Continuous current Output voltage 14V DC see Figure 9 Intermittent current 1 Output voltage 14V DC see Figure 9 Overload short circuit current Max 6 7 A Continuous current see Figure 9 Typ 8 6 A Inter...

Страница 10: ...ring this time Attributes Values Notes AC 100V AC 120V AC 230V Hold up Time Typ 40 ms 60 ms 242 ms At 24V 1 9 A See Figure 11 Min 32 ms 48 ms 194 ms At 24V 1 9 A See Figure 11 Typ 14 ms 25 ms 119 ms A...

Страница 11: ...5 A 25 at 3 8 A Power losses Typ 0 3 W 0 3 W 0 4 W At no load Typ 5 0 W 4 3 W 3 8 W At 24V 1 9 A half load Typ 9 5 W 7 9 W 6 0 W At 24V 3 8 A full load Figure 13 Efficiency Versus Output Current at 24...

Страница 12: ...C OK Status Indicator Power Converter Figure 18 Front Side User Elements 1 Output terminals screw terminals Dual terminals for the negative and positive pole Both poles are internally connected Positi...

Страница 13: ...hat statistically one unit fails every 100 hours if 10 000 units are installed in the field However it cannot be determined if the failed unit has been running for 50 000 hr or only for 100 hr For the...

Страница 14: ...age on input EN 61000 4 5 L N 2 kV Criterion A N L PE 4 kV Criterion A Surge voltage on output EN 61000 4 5 1 kV CriterionA PE 1 kV CriterionA Conducted disturbance EN 61000 4 6 0 15 80 MHz 10V Criter...

Страница 15: ...7 1 non conductive Vibration sinusoidal 1 2 17 8 Hz 1 6 mm 0 063 in 17 8 500 Hz 2 g 2 hours axis According to IEC 60068 2 6 Shock 1 30 g 6 ms 20 g 11 ms 3 bumps direction 18 bumps intotal According to...

Страница 16: ...500V DC Min 500 M At delivered condition between output and PE measured with 500V DC Output overvoltage protection Typ 30 5V DC Max 32V DC If there is ananomaly inside the power supply aredundant cir...

Страница 17: ...and laboratory use Part 2 201 Particular requirements for control equipment ANSI UL 61010 2 201 former UL 508 planned Listed as Open Type Device for use in Control Equipment UL Category NMTR NMTR7 E F...

Страница 18: ...EN 50022 witha heightof7 5 mm 0 295 in or 15 mm 0 59 in Housing material High grade polycarbonate ABS blend material Installation clearances Keep the following min installation clearances 40 mm 1 57 i...

Страница 19: ...or fuses If there is a short or an overload in one branch circuit the fuse or circuit breaker need a certain amount of overcurrent to open in a timely manner This avoids voltage loss in adjacent circ...

Страница 20: ...lleled for 1 1 redundancy to gain higher system availability Redundant systems require a certain amount of extra power to support the load in case one device fails The simplest way is to put two devic...

Страница 21: ...e is placed in the middle of the box and no other heat producing items are inside the box The load is placed outside the box The temperature sensor inside the box is placed in the middle of the right...

Страница 22: ...applications in which the 1606 XLB90E power supply shall not be used DC Input Do not operate this power supply with DC input voltage Charging of Batteries Do not use the power supply to charge batteri...

Страница 23: ...losures and Contact Ratings Specifications publication IC TD002 Provides a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application In...

Страница 24: ...dgebase Access Knowledgebase articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installati...

Отзывы: