10
Rockwell Automation Publication 1606-RM121A-EN-P - October 2020
Hold-up Time
The hold-up time is the time during which the output voltage of a power supply
remains within specification following the loss of input power. The hold-up
time is dependent on output load. At no load, the hold-up time can be up to
several seconds. The green DC OK status indicator is also on during this time.
Attributes
Values
Notes
AC 100V
AC 120V
AC 230V
Hold-up Time
Typ
40 ms
60 ms
242 ms
Min
32 ms
48 ms
194 ms
At 24V, 1.9 A. See
Typ
14 ms
25 ms
119 ms
At 24V, 3.8 A. See
Min
11.5 ms
20 ms
95 ms
At 24V, 3.8 A. See
Figure 11 - Hold-up Time Versus Input Voltage
Figure 12 - Shut-down Behavior, Definitions
0
20
40
100
120 ms
90
120
155
190
230V AC
Input Voltage
Hold-up Time
60
80
a) 24V 1.9 A typ
b) 24V 1.9 A min
c) 24V 3.8 A typ
d) 24V 3.8 A min
a
b
c
d
- 5%
Hold-up Time
Zero Transition
Output
Voltage
Input
Voltage