Connection Terminals

The terminals are IP20 fingersafe constructed and are suitable for field wiring 
and factory wiring. Ensure that all strands of a stranded wire enter the 
terminal connection. The use of ferrules is recommended.

Lifetime Expectancy

The lifetime expectancies that are shown in the table indicate the minimum 
operating hours (service life). The lifetime expectancy of the built-in 
electrolytic capacitors determines the lifetime expectancy of the power supply. 
Lifetime expectancy is specified in operational hours and is calculated 
according to the manufacturer specification of the capacitor.

The manufacturer of the electrolytic capacitors only states a maximum life of 
up to 15 years (131,400 hr). Any number that exceeds this value is a calculated 
theoretical lifetime, which can be used to compare devices.

Mean Time Between Failure

Mean Time Between Failure (MTBF) is calculated according to statistical 
device failures, and indicates reliability of a device. The MTBF value is a 
statistical representation of the likelihood of a unit to fail and does not 
necessarily represent the life of a product. An MTBF value of, for example, 
1,000,000 hr means that statistically one unit fails every 100 hours if 10,000 
units are installed in the field. However, it cannot be determined if the failed 
unit has been running for 50,000 hr or only for 100 hr.

For these types of units, the Mean Time To Failure (MTTF) value is the same as 
the MTBF value.

Attributes

Descriptions

Type

Screw terminals

Solid wire

6 mm

2

 max

Stranded wire

4 mm

2

 max

American Wire Gauge

AWG 20…10

Wire diameter max (including ferrules)

2.8 mm (0.11 in.)

Wire stripping length

7 mm (0.28 in.)

Recommended tightening torque

1 N•m (9 lb•in)

Screwdriver

3 mm (0.12 in.) slotted or Phillips No 1

Attributes

Values

Notes

AC 100V

AC 120V

AC 230V

Lifetime expectancy

260,000 hr

292,000 hr

309,000 hr

At 24V, 1.9 A and 40 °C (104 °F)

640,000 hr

720,000 hr

815,000 hr

At 24V, 1.9 A and 25 °C (77 °F)

39,000 hr

64,000 hr

102,000 hr

At 24V, 3.8 A and 40 °C (104 °F)

91,000 hr

147,000 hr

287,000 hr

At 24V, 3.8 A and 25 °C (77 °F)

Attributes

Values

Notes

AC 100V

AC 120V

AC 230V

MTBF SN 29500, IEC 61709

1,174,000 hr

1,273,000 hr

1,507,000 hr

At 24V, 3.8 A and 40 °C (104 °F)

2,251,000 hr

2,406,000 hr

2,752,000 hr

At 24V, 3.8 A and 25 °C (77 °F)

MTBF MIL HDBK 217F

751,000 hr

760,000 hr

698,000 hr

At 24V, 3.8 A, 40 °C (104 °F); Ground Benign GB40

1,085,000 hr

1,099,000 hr

1,018,000 hr

At 24V, 3.8 A, 25 °C (77 °F); Ground Benign GB25

219,000 hr

224,000 hr

220,000 hr

At 24V, 3.8 A, 40 °C (104 °F); Ground Fixed GF40

288,000 hr

294,000 hr

293,000 hr

At 24V, 3.8 A, 25 °C (77 °F); Ground Fixed GF25

Содержание Allen-Bradley 1606-XLB90E

Страница 1: ...DC Power Supply 24V 3 8 A 90 W Single phase Input Catalog Number 1606 XLB90E Reference Manual Original Instructions...

Страница 2: ...y Rockwell Automation Inc with respect to use of information circuits equipment or software described in this manual Reproduction of the contents of this manual in whole or in part without written per...

Страница 3: ...Terminals 13 Lifetime Expectancy 13 Mean Time Between Failure 13 Electromagnetic Compatibility 14 Environment 15 Safety and Protection Features 16 Dielectric Strength 16 Approvals 17 Other Fulfilled...

Страница 4: ...4 Rockwell Automation Publication 1606 RM121A EN P October 2020 Notes...

Страница 5: ...compromising quality or reliability Width only 36 mm 1 42 in Efficiency up to 93 8 Low no load power losses Full power between 10 60 C 14 140 F Large screw terminals Terms Descriptions PE The abbrevia...

Страница 6: ...0 158 F Input voltage AC AC 100 240V 10 Mains frequency 50 60 Hz 6 Input current AC 1 45 A 0 95 A At 120 230V AC Power factor 0 58 0 45 At 120 230V AC Input inrush current 18 A peak 40 A peak At 120 2...

Страница 7: ...aker Attributes Values Notes AC 100V AC 120V AC 230V Input current Typ 1 69 A 1 45 A 0 95 A At 24V 3 8 A see Figure 3 Power factor Typ 0 6 0 58 0 45 At 24V 3 8 A see Figure 4 Start up delay Typ 50 ms...

Страница 8: ...ld start Typ 14 Apeak 18 Apeak 40 Apeak At 40 C 104 F ambient cold start Max 15 Apeak 20 Apeak 43 Apeak At 25 C 77 F ambient cold start Typ 12 Apeak 16 Apeak 35 Apeak At 25 C 77 F ambient cold start I...

Страница 9: ...Continuous current Output voltage 14V DC see Figure 9 Intermittent current 1 Output voltage 14V DC see Figure 9 Overload short circuit current Max 6 7 A Continuous current see Figure 9 Typ 8 6 A Inter...

Страница 10: ...ring this time Attributes Values Notes AC 100V AC 120V AC 230V Hold up Time Typ 40 ms 60 ms 242 ms At 24V 1 9 A See Figure 11 Min 32 ms 48 ms 194 ms At 24V 1 9 A See Figure 11 Typ 14 ms 25 ms 119 ms A...

Страница 11: ...5 A 25 at 3 8 A Power losses Typ 0 3 W 0 3 W 0 4 W At no load Typ 5 0 W 4 3 W 3 8 W At 24V 1 9 A half load Typ 9 5 W 7 9 W 6 0 W At 24V 3 8 A full load Figure 13 Efficiency Versus Output Current at 24...

Страница 12: ...C OK Status Indicator Power Converter Figure 18 Front Side User Elements 1 Output terminals screw terminals Dual terminals for the negative and positive pole Both poles are internally connected Positi...

Страница 13: ...hat statistically one unit fails every 100 hours if 10 000 units are installed in the field However it cannot be determined if the failed unit has been running for 50 000 hr or only for 100 hr For the...

Страница 14: ...age on input EN 61000 4 5 L N 2 kV Criterion A N L PE 4 kV Criterion A Surge voltage on output EN 61000 4 5 1 kV CriterionA PE 1 kV CriterionA Conducted disturbance EN 61000 4 6 0 15 80 MHz 10V Criter...

Страница 15: ...7 1 non conductive Vibration sinusoidal 1 2 17 8 Hz 1 6 mm 0 063 in 17 8 500 Hz 2 g 2 hours axis According to IEC 60068 2 6 Shock 1 30 g 6 ms 20 g 11 ms 3 bumps direction 18 bumps intotal According to...

Страница 16: ...500V DC Min 500 M At delivered condition between output and PE measured with 500V DC Output overvoltage protection Typ 30 5V DC Max 32V DC If there is ananomaly inside the power supply aredundant cir...

Страница 17: ...and laboratory use Part 2 201 Particular requirements for control equipment ANSI UL 61010 2 201 former UL 508 planned Listed as Open Type Device for use in Control Equipment UL Category NMTR NMTR7 E F...

Страница 18: ...EN 50022 witha heightof7 5 mm 0 295 in or 15 mm 0 59 in Housing material High grade polycarbonate ABS blend material Installation clearances Keep the following min installation clearances 40 mm 1 57 i...

Страница 19: ...or fuses If there is a short or an overload in one branch circuit the fuse or circuit breaker need a certain amount of overcurrent to open in a timely manner This avoids voltage loss in adjacent circ...

Страница 20: ...lleled for 1 1 redundancy to gain higher system availability Redundant systems require a certain amount of extra power to support the load in case one device fails The simplest way is to put two devic...

Страница 21: ...e is placed in the middle of the box and no other heat producing items are inside the box The load is placed outside the box The temperature sensor inside the box is placed in the middle of the right...

Страница 22: ...applications in which the 1606 XLB90E power supply shall not be used DC Input Do not operate this power supply with DC input voltage Charging of Batteries Do not use the power supply to charge batteri...

Страница 23: ...losures and Contact Ratings Specifications publication IC TD002 Provides a quick reference tool for Allen Bradley industrial automation controls and assemblies Safety Guidelines for the Application In...

Страница 24: ...dgebase Access Knowledgebase articles rok auto knowledgebase Local Technical Support Phone Numbers Locate the telephone number for your country rok auto phonesupport Literature Library Find installati...

Отзывы: