14
Rockwell Automation Publication 1606-RM121A-EN-P - October 2020
Electromagnetic
Compatibility
The electromagnetic compatibility (EMC) behavior of the device is designed
for applications in industrial, residential, commercial, and light industrial
environments.
The device is investigated according to EN 61000-6-1, EN 61000-6-2,
EN 61000-6-3, and EN 61000-6-4.
EMC immunity information is provided in the following table.
EMC emission information is provided in the following table.
Switching frequency information is provided in the following table.
Attributes
Standards
Values
Criteria
(1)
(1)
Criterion A: The device shows normal operation behavior within the defined limits.
Criterion B: The device operates continuously during and after the test. During the test, minor temporary
impairments may occur. If they do occur, the device corrects them.
Criterion C: Temporary loss of function is possible. The device may shut down. If it shuts down, it then restarts by
itself. No damage or hazards for the device occur.
Electrostatic discharge
EN 61000-4-2
Contact discharge
8 kV
Criterion A
Air discharge
8 kV
Criterion A
Electromagnetic RF field
EN 61000-4-3
80 MHz…2.7 GHz
10V/m
Criterion A
Fast transients (Burst)
EN 61000-4-4
Input lines
4 kV
Criterion A
Output lines
2 kV
Criterion A
DC OK Signal
(coupling clamp)
2 kV
Criterion A
Surge voltage on input
EN 61000-4-5
L
N
2 kV
Criterion A
N / L
PE
4 kV
Criterion A
Surge voltage on output
EN 61000-4-5
+
-
1 kV
Criterion A
+ / -
PE
1 kV
Criterion A
Conducted disturbance
EN 61000-4-6
0.15…80 MHz
10V
Criterion A
Mains voltage dips
EN 61000-4-11
0% of 100V AC
0V AC, 20 ms
Criterion B
40% of 100V AC
40V AC, 200 ms
Criterion C
70% of 100V AC
70V AC, 500 ms
Criterion A
0% of 120V AC
0V AC, 20 ms
Criterion A
40% of 120V AC
48V AC, 200 ms
Criterion C
70% of 120V AC
84V AC, 500 ms
Criterion A
0% of 200V AC
0V AC, 20 ms
Criterion A
40% of 200V AC
80V AC, 200 ms
Criterion A
70% of 200V AC
140V AC, 500 ms
Criterion A
Voltage interruptions
EN 61000-4-11
—
0V AC, 5000 ms
Criterion C
Powerful transients
VDE 0160
Over entire load range
750V, 1.3 ms
Criterion A
Attributes
Standards
Notes
Conducted emission input lines
EN 55011, EN 55022, FCC Part 15, CISPR 11, CISPR 22
Class B
Conducted emission output lines
IEC/CISPR 16-1-2, IEC/CISPR 16-2-1
Limits for local DC power networks fulfilled.
Radiated emission
EN 55011, EN 55022, CISPR 11, CISPR 22
Class B
Harmonic input current
EN 61000-3-2
Fulfilled (Class A)
Voltage fluctuations, flicker
EN 61000-3-3
Fulfilled, tested with non-pulsing constant current loads.
This device complies with FCC Part 15 rules.
Operation is subjected to following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
Attribute
Values
Notes
Main converter
40…140 kHz