Rockwell Automation Publication 1606-RM117A-EN-P - July 2020
9
Output
The output provides a SELV/PELV/ES1 rated voltage, which is galvanically
isolated from the input voltage.
The output is electronically protected against no-load, overload, and short
circuit. If there is a protection event, audible noise may occur.
The output is designed to supply any kind of loads, including inductive and
capacitive loads. Capacitive loads should not be larger than 2200 μF with 5 A or
8000 μF with 2.5 A additional current load.
At heavy overloads (when output voltage falls below 8V), the device delivers
continuous output current for 20 ms. After the 20 ms have passed, the output
is switched off for 170 ms before a new start attempt is automatically
performed. This cycle is repeated as long as the overload exists.
Attributes
Values
Notes
Output voltage
Nom
DC 12V
—
Adjustment range
Min
12…15V
Guaranteed value
Max
15.5V
This is the max output voltage that can occur at the clockwise end position of the
potentiometer due to tolerances. It is not guaranteed that this value can be achieved.
Factory settings
Typ
12V
±0.2%, at full load and cold unit
Line regulation
Max
10 mV
Between 90…300V AC
Load regulation
Max
100 mV
Between 0…5 A, static value, see
Ripple and noise voltage
Max
100 mVpp
Bandwidth 20 Hz to 20 MHz, 50 Ω
Output current
Nom
5.0 A
At 12V and an ambient temperature below 60 °C (140 °F)
Nom
3.8 A
At 12V and 70 °C (158 °F) ambient temperature
Nom
4.0 A
At 15V and an ambient temperature below 60 °C (140 °F)
Nom
3.0 A
At 15V and 70 °C (158 °F) ambient temperature
Overload behavior
—
Continuous current
Output voltage above 8V DC, see
—
Intermittent current
Output voltage below 8V DC, see
Overload/ short-circuit current
Max
7.0 A
Continuous current, see
Typ
9.0 A
Intermitted current peak value for 25 ms typ, Load impedance 150 mΩ, see
.
Discharge current of output capacitors is not included.
Max
3.2 A
Intermitted current average value (R.M.S.) Load impedance 150 mΩ, see
Output capacitance
Typ
2200 µF
Included inside the power supply
Back-feeding loads
Max
16V
The unit is resistant and does not show malfunctioning when a load feeds back voltage to
the power supply. It does not matter whether the power supply is on or off. The absorbing
energy can be calculated according to the built-in large sized output capacitor.
Figure 10 - Output Voltage Versus Output Current, Typ
Figure 11 - Intermittent Current at Short Circuit, Typ
Output Voltage
0
0
1
8V
15V
12V
9 A
3
2
4
5
6
7
8
Adju stment ra nge
Output Current
A
B
A: continuous current
B: intermittent current
Output
Current
0
9 A
170 ms
170 ms
170 ms
20
ms
t
Short -circuit
Normal
operation
Normal
operation
20
ms
20
ms