Rockwell Automation Publication 1606-RM117A-EN-P - July 2020
Input Inrush Current
An NTC limits the input inrush current after turn-on of the input voltage. The
inrush current is input voltage and ambient temperature dependent. The
output load has no impact on the inrush current value.
The charging current into EMI suppression capacitors is disregarded in the
first microseconds after switch-on.
Attributes
Values
Notes
AC 100V
AC 120V
AC 230V
Inrush current
Typ
12 A
peak
15 A
peak
36 A
peak
At 40 °C (104 °F) ambient, cold start
Typ
10 A
peak
12 A
peak
30 A
peak
At 25 °C (77 °F) ambient, cold start
Max
15 A
peak
18 A
peak
44 A
peak
At 40 °C (104 °F) ambient, cold start
Max
12 A
peak
15 A
peak
36 A
peak
At 25 °C (77 °F) ambient, cold start
Inrush energy
Max
0.2 A
2
s
0.3 A
2
s
1.4 A
2
s
At 40 °C (104 °F) ambient, cold start
Figure 6 - Typical Turn-on Behavior at 120V AC and 25 °C (77 °F) Ambient
Figure 7 - First Inrush Peak at 120V AC and 25 °C (77 °F) Ambient
Figure 8 - Typical Turn-on Behavior at 230V AC and 25 °C (77 °F) Ambient
Figure 9 - First Inrush Peak at 230V AC and 25 °C (77 °F) Ambient