![Rockwell Automation Allen-Bradley 1606-XLB60BH Скачать руководство пользователя страница 16](http://html1.mh-extra.com/html/rockwell-automation/allen-bradley-1606-xlb60bh/allen-bradley-1606-xlb60bh_manual_1475738016.webp)
16
Rockwell Automation Publication 1606-RM117A-EN-P - July 2020
Environment
Attributes
Values
Notes
Operational temperature
-10…+70 °C (14…158 °F)
The operational temperature is the ambient or surrounding temperature
and is defined as the air temperature 2 cm (0.79 in.) below the device.
Storage temperature
-40…+85 °C (-40…+185 °F)
For storage and transportation
Output derating
0.12 A/1 °C (0.12 A/1.8 °F)
Between 60…70 °C (140…158 °F)
0.3 A/1000 m (0.3 A/3281 ft) or
5 °C/1000 m (9 °F/3281 ft)
For altitudes above 2000 m (6562 ft), see
Hardware does not control the derating. You must take this into consideration to stay below the derated current
limits to prevent overloading the unit.
Humidity
5…95% r.H.
According to IEC 60068-2-30 No condensation allowed.
Atmospheric pressure
110…54 kPa
See
for details
Altitude
Up to 5000 m (16,404 ft)
See
for details
Overvoltage category
II
According to IEC 60664-1, for altitudes up to 5000 m (16,404 ft)
Impulse withstand voltage
4 kV
(according to overvoltage category III)
Input to PE
According to IEC 60664-1, for altitudes up to 2000 m (6562 ft)
Degree of pollution
2
According to IEC 60664-1, non-conductive
Vibration sinusoidal
2…17.8 Hz: ±1.6 mm (0.063 in.)
17.8…500 Hz: 2 g
2 hours / axis
According to IEC 60068-2-6
Shock
30 g 6 ms, 20 g 11 ms
3 bumps / direction 18 bumps in total
According to IEC 60068-2-27
Shock and vibration are tested in combination with DIN rails according to EN 60715 with a height of 15 mm (0.59 in.)
and a thickness of 1.3 mm (0.05 in.).
LABS compatibility
As a rule, only non-silicon precipitating materials are used. The unit conforms to the LABS criteria and is suitable for
use in paint shops.
Corrosive gases
Compliant to ISA-71.04-1985, Severity Level G3 and IEC 60068-2-60 Test Ke Method 4 for a service life of 10 years min in
these environments.
Figure 20 - Output Power Versus Ambient Temperature
Figure 21 - Output Power Versus Altitude
Allowed Output Current at 12V
0
-10
0
+70 °C
3.8 A
5.0 A
+60
B
A
Ambient Temperature
A...continuous
B... short term (300 s max)
2000
5000 m
4.1 A
4.7 A
5.0 A
Altitude
Allowed Output Current at 12V
B
C
A... Tamb < 60 °C
B... Tamb < 50 °C
C... Tamb < 45 °C
A
AP
(1)
80
54 kPa
110
0
(1) Atmospheric pressure
4000
62