Mean Time Between Failure
Mean Time Between Failure (MTBF) is calculated according to statistical
device failures, and indicates reliability of a device. It is the statistical
representation of the likelihood of a unit to fail and does not necessarily
represent the life of a product.
The MTBF value is a statistical representation of the likelihood of a device to
fail. An MTBF value of, for example, 1,000,000 h means that statistically one
unit fails every 100 hours if 10,000 units are installed in the field. However, it
cannot be determined if the failed unit has been running for 50,000 h or only
for 100 h.
For these types of units, the Mean Time To Failure (MTTF) value is the same as
the MTBF value.
Electromagnetic
Compatibility
The electromagnetic compatibility (EMC) behavior of the device is designed
for applications in industrial, residential, commercial, and light industrial
environments.
The device complies with EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN
61000-6-4, EN 61000-3-2, and EN 61000-3-3.
The device complies with FCC Part 15 rules. Operation is subjected to following
two conditions: (1) this device may not cause harmful interference, and (2) this
device must accept any interference received, including interference that may
cause undesired operation.
Do not use this device in an application where both of the following are true:
•
The device is used on AC 100V mains with more than 3.6 A load.
•
The application is sensitive to short output voltage dips during mains
interruptions, even with a length shorter than 20 ms.
Attributes
Values (in kilohours)
Notes
AC 100V
AC 120V
AC 230V
MTBF SN 29500, IEC 61709
1542 khr
1649 khr
1673 khr
At 12V, 5 A and 40 °C (104 °F)
2768 khr
2911 khr
2925 khr
At 12V, 5 A and 25 °C (77 °F)
MTBF MIL HDBK 217F
695 khr
707 khr
685 khr
At 12V, 5 A, 40 °C (104 °F); Ground Benign GB40
(1)
(1)
Ground Benign (GB): A non-mobile, temperature and humidity controlled environment that is readily accessible to
maintenance. Includes laboratory instruments and test equipment, medical electronic equipment, business and scientific
computer complexes, and missiles and support silos in ground silos.
993 khr
1008 khr
982 khr
At 12V, 5 A, 25 °C (77 °F); Ground Benign GB25
189 khr
192 khr
197 khr
At 12V, 5 A, 40 °C (104 °F); Ground Fixed GF40
(2)
(2) Ground Fixed (GF): Moderately controlled environments such as installations in permanent racks with adequate cooling air
and possible installation in unheated buildings. Includes permanent installation of air traffic control radar and
communication facilities.
246 khr
250 khr
258 khr
At 12V, 5 A, 25 °C (77 °F); Ground Fixed GF25