3.0  COMBUSTION ADJUSTMENT   

Preset values for proper combustion are set during First boiler start up by choosing Burner size. However 
there are situations where correction has to be made for good combustion. Chimney draft, pellet types or 
oxygen inside the room can influence proper combustion.  

There is function inside Plumber settings for this reason, where you can change fan speed and number of 
pellets going on the grate by %.  

 

o

 

Flame parameters 

 

By flame size and color you are able to correct combustion folowing examples below:  

 

Low pellets 

 

Flame  is  small.  Doesn‘t  touch  the  opposite  wall  of  the  boiler. 
Then you should increase fan speed or pellet quantity.  

 

 

High pellets 

 

Flame  is  to  long. If  you open top  doors  flame  goes  out  of the 
boiler. Often red color and black ends. Then you should decrease 
fan speed or pellet quantity.  

 

 

Low O2 

 

If  there  is  not  enough  O2  inside  the  boiler,  the  flame has  red 
color with dark smoke comming from the chimney. You have to 
decrease number of pellets, or increase fan speed. 

 

 

High O2 

 

If there is a lot of O2 inside the boiler, than the flame is yellow 
with  really  agresive  look.  Often  small  as  well.  You  have  to 
decrease fan speed, or increase number of pellets. 

 

 

Correct flame 

 

Flame should be orange collor and should touch the opposit wall of the boiler. Below you can find 
two functions which are used for combustion correction in %. Use these functions to correct the 
flame during operation. 

 

 

min power 

 

max power

 

 

Содержание BIOPEL

Страница 1: ...Biopel Pellet Boiler Installation manual...

Страница 2: ...ibed here in this manual It is recommended to study the menus prior to initial start Save this manual so you always have it available when needed Page 3 Comments on the Manual Page 4 The Clean Air Act...

Страница 3: ...indication of improper draft of the chimney all operation of your system mustceaseimmediately and mustremain so until a solution to thedraftproblem has been resolved Continuing operation may result i...

Страница 4: ......

Страница 5: ...se countries Separate legislation the Clean Air Northern Ireland Order 1981 applies in Northern Ireland Therefore it is a requirement that fuels burnt or obtained for use in smoke control areas have b...

Страница 6: ...uts as the seal between the boiler and the burner can leak over time 4 Make sure that the burner is horizontal and that all connections are tight Burner description The main parts of the burner are th...

Страница 7: ...ler for burner installation However the opposite flange on the boiler bust be always sealed For example if you choose left flange for burner connection make sure that right flange is properly sealed B...

Страница 8: ...le located on the top of the burner and secure with 2 x burner pipe screws Attach PVC tube on the burner pipe and from the other side on the external auger outlet You can cut the PVC tube if necessary...

Страница 9: ...nt ignition of the boiler and will prolong the life of the igniter The min buffer thermal store capacity should be 10 litres kW output eg 200 litres for Biopel 20 The load valve supplied with the boil...

Страница 10: ...and connection board are pre wired with simple plugs to allow for quick installation When using the Compact type hopper the connection board can be fixed to the sloping wall of the hopper near the bur...

Страница 11: ...is the boiler pump ROOM REGULATOR Room thermostat volt free Other connections for optional accessories are DHW PUMP Used to control a pump or 2 port valve for hot water production KOMPRESSOR Connecti...

Страница 12: ......

Страница 13: ...t is designed to offer the home owner and installer a series of simple menus to give full control of all boiler settings and parameters The controller has 3 levels of PIN protection in order to preven...

Страница 14: ...t the same time o Summer mode sets the burner power to an half value To be specific Feed time max and Feed interval min is reduced to half Cleaning cleaning of the grate during PID modulation work o A...

Страница 15: ...rection correction of fan speed 50 Power factor correction of burner power Changes values in Feeder time max and Feeder interval min in range of 50 Example if you set 30 in Auger correction 30 it mean...

Страница 16: ...at the size in Kw is correct 5 Burner size changes values in Service settings shown below 6 Auger setup Ignition a Feed time for how long pellet auger supplies pellets on the burner grate b Fan speed...

Страница 17: ...d increase fan speed or pellet quantity High pellets Flame is to long If you open top doors flame goes out of the boiler Often red color and black ends Then you should decrease fan speed or pellet qua...

Страница 18: ...for PID regulation is lower which means speed of the fan is decreased in all PID modulation range Power correction Power correction is responsible for changing number of pellets going on the grate You...

Страница 19: ...removing the ash from the chimney flue Never dispose of hot ashes in the trash but let it cool in a metal bucket Hot ashes can re ignite Burner head Remove any ash or cinders from the grate Remove an...

Страница 20: ...perform service Please note that service indicators are only expectations based on experience Components can easily have a longer lifetime than suggested by the service indicator It is recommended to...

Страница 21: ...e correct positioning Burnergrate rests on support ledge Burnergrate upstand at this end Burnergrate correctlypositioned Burnergrate upstand locked in burner Burner grate incorrect positioning Burner...

Страница 22: ...n receipt If the buyer declares that the delivery was inadequate or defective the customer must immediately and without delay make a written claim with Robus Energy Returns are only made by agreement...

Страница 23: ......

Отзывы: