RB100 : Installation and Use Manual
36
Ed. 06/2014 – FW version
1.002
How to connect a CAN BUS cable to a DDC
Have
access to DDC rear cover.
1. Place jumpers on DDC according to node type to be configured. If necessary, open
DDC rear cover by untightening four screws; after properly positioning jumpers, re-
close the cover and re-tighten 4 screws.
"J21" jumper positions are shown in two figures below:
- if DDC is an
intermediate node
on the network (6 wires in "P8" orange connector):
locate jumpers on DDC as shown in Figure 18: OPENED.
Figure 18 -
Connection of 2 CAN BUS cables to DDC: DDC IS AN INTERMEDIATE NODE. The positions of CAN BUS
cable wires and “H21” jumpers are pointed out: OPENED.
- if DDC is a
final node
on the network (3 wires in "P8" orange connector): locate
jumpers on DDC as shown in Figure 19: CLOSED.
Figure 19 -
Connection of 1 CAN BUS cable to DDC: DDC IS A FINAL NODE. The positions of CAN BUS cable wires
and “H21” jumpers are pointed out: CLOSED.
Scheda
DDC
J21
jumpers:
CLOSED
DDC
board
J21
jumpers:
OPENED