![Robur Line MC Series Скачать руководство пользователя страница 43](http://html1.mh-extra.com/html/robur/line-mc-series/line-mc-series_installation-use-and-maintenance-manual_1471536043.webp)
Technical assistance and maintenance
Ed. 04/2007
43
Does the flue fan
stop and go?
Replace the anti-welding
device of pressure switch
Does the electrode start
sparking in the burner
after 30 seconds?
Check the ignition electrode and
related cable. Is the electrode
properly positioned and does the
cable touch any of the unit's metal
parts?
Is the control unit
fuse broken?
Replace the
control unit…
Replace the
ignition electrode
Replace the
fuse
Reset the
control unit
Reverse the supply
connection (live and
neutral)
Replace the flame
sensor…
The burner starts but
stops soon after the end of
the spark train
Check the phase.
Is it correct?
Check the flame sensor.
Is it bent
or does it touch the burner?
Replace the
control unit…
Restart the
control unit
Locate the causes for
gas supply failure
Replace the
gas valve
Check gas supply
mains. Is there gas?
Check valve voltage. Is
there voltage in the gas
valve?
The burner starts
(or gas is present)
Replace the ignition
control unit
Replace the
thermostat
Check fan thermostat for
correct operation. Is it
locked out?
Fan starts after a
few minutes?
Replace the capacitor. If
the failure persists,
replace the fan motor.
Unit is operating
properly
continued
YES
NO
NO
YES
NO
YES
YES
YES
NO
YES
YES
YES
NO
NO
NO
YES
NO
YES
NO
YES
YES
NO
NO
YES