M C Series – Warm air heaters – Installation, Operation and Maintenance Manual
22
Ed.
04/2007
Figure 11
– Flue pipe set-up if a mixing chamber is used
If a mixing chamber is installed (available as an accessory – see ACCESSORIES on page
45), in order to prevent combustion gases coming into contact with the heated
environment it is important to avoid positioning the flue pipe outlet within the clearance
area indicated in Figure 12.
Figure 12
– Clearance area for flue pipe outlet of M C series heaters with mixing chamber
mixing chamber
1.5 m
1.5 m
1,5 m
CLEARANCE AREA
EXTERNAL AIR INTAKE GRILLE
ATTENTION:
DO NOT POSITION THE EXHAUST OUTLET IN THE CLEARANCE AREA INDICATED