End user
Ed. 2014-08
55
COMPLETE THE START UP PROCEDURE AND THEN SWITCH THE UNITS OFF IF:
‐
The clearances have not been respected (see Figure 3 on page 16).
‐
The static pipeline gas pressure does not comply with the Robur specifications
indicated in the Robur Installation Manual (see Table 13 on page 25) and data
plate.
‐
The dynamic pipeline gas pressure does not comply with the Robur specifications
indicated in the Robur Installation Manual (see Table 13 on page 25) and data
plate.
COMPLETE THE START UP PROCEDURE AND ALLOW THE UNITS TO
TEMPORARILY RUN WHEN:
‐
The water strainer is missing or incorrectly installed.
‐
The expansion vessel is missing.
‐
The shut-off gas valve near the unit is missing.
‐
The Can-Bus cable is not compliant with Robur specifications.
‐
The control system is not supplied by a dedicated electrical transformer.
Fill out the start up report mentioning the following sentence: “The unit has been started
temporarily because …..".
It is the user/installer responsibility to fix the non conformities of the installation indicated
by the Service Company.
4.7 MAINTENANCE
Correct maintenance prevents problems, guarantees maximum operating efficiency of the
appliance and allows running costs to be contained.
The maintenance of the unit must be performed by authorized Robur personnel.
Label all wires prior to disconnection when servicing controls. Wiring errors can
cause improper and dangerous operation.
Verify proper operation after servicing.
Switch
off the power of the unit and DDC
before doing any maintenance
operation.
Maintenance operations can not be performed by the end user.