GAHP-W – Installation, start-up, use and maintenance manual
28
Edition:
2014-08
PROPYLENE GLYCOL CAPACITY CORRECTION FACTOR TABLE
Percent Propylene Glycol
15% 20% 25% 30% 35% 40% 50%
Approximate Freezing Point In °F
25° 21° 17° 11° 5° 0° -10°
Capacity Factor Multiplier *
0.98 0.96 0.95 0.93 0.92 0.91 0.89
Pressure Drop Multiplier **
1.08 1.11 1.16 1.21 1.27 1.32 1.38
* At Standard ARI 590
conditions: 54°F entering fluid temperature, 44°F leaving fluid temperature, 95°F ambient temperature, 0.0005
fouling
** Pressure Drops may vary with individual glycol manufacturer’s products. The information provided for pressure drop is typical but
installing contractor / project engineer is responsible for verification of pressure drop correction based on specifications of glycol
used.
Table 16 -
Approximate water freezing point temperatures. The value are strongly affected by the type of
antifreeze/glycol used.
The manufacturer will not be held responsible or liable for any damage caused by
incorrect use or disposal of the glycol/antifreeze.