Overview and technical specifacions
Ed. 2014-08
9
GAHP-W – HEATING AND CHILLING CAPACITIES
Table 3
-
GAHP-W heating capacity. DT is the difference between outlet and inlet temperature.
Table 4
-
GAHP-W chilling capacity. DT is the difference between outlet and inlet temperature.
GAHP-W HEATING CAPACITY - kBtu/hr
HOT WATER INLET TEMPERATURE
77.0 86.0 95.0 104.0 113.0 113.0
CHILLED
WATER INLET
TEMPERATURE
DT=18 DT=36
46.4 142.4 140.0 136.0 129.0 121.5 117.7
50.0 142.6 140.9 138.2 132.4 125.3 121.3
53.6 142.6 141.4 139.6 134.9 128.8 124.8
59.0 142.6 141.6 140.5 137.6 133.3 129.4
68.0 142.6 141.6 140.7 139.5 137.7 134.7
77.0 142.6 141.6 140.7 139.7 138.8 137.0
86.0 142.6 141.6 140.7 139.7 138.8 137.2
GAHP-W CHILLING CAPACITY - kBtu/hr
HOT WATER INLET TEMPERATURE
77.0 86.0 95.0 104.0 113.0 113.0
CHILLED
WATER INLET
TEMPERATURE
DT=18 DT=36
46.4 63.7 61.2 56.7 51.7 46.0 42.5
50.0 64.1 62.2 58.9 54.8 49.9 46.0
53.6 64.2 62.9 60.6 57.4 53.3 49.0
59.0 64.3 63.6 62.4 60.4 57.1 52.9
68.0 64.3 64.0 63.5 62.4 60.6 57.9
77.0 64.3 64.0 63.5 62.4 61.6 60.1
86.0 64.3 64.0 63.5 62.4 61.7 60.0