Electrical connections
Ed. 2014-08
39
•
If the electrical consumption of each water pump (heating and cooling) is higher than
4A, the pumps must be connected using two relays.
PY is the cooling water pump, R2 is the cooling pump relay.
PW is the heating water pump, R1 is the heating pump relay.
Open the jumpers J10.
Figure 18 -
Connection of water pumps with electrical consumption higher than 4A
•
Example of water pump connections with more than one appliance.
PY is the cooling water pump, KPY is the cooling pump relay
PW is the heating water pump, KPW is the heating pump relay
PTR is the Low Voltage transformer
IP is the water pumps main switch
Open the jumpers J10