VFD unit setup
Run the machine in setup mode (the drive must be stopped). To change
or view parameter value, press ENTER, the display shows
00.__
Then
use up or down keys to choose the first two digits of the parameter (for
example,
02.
). Now press ENTER again, display shows
02.00
. Use up or
down keys to choose the second two digits of the parameter, for example,
02.11
. Press ENTER again to see the current value of the parameter.
Change value, if needed, with up or down keys. Press ENTER to confirm
and save the new value, the display shows End. Now use MODE button
to return back to the previous level of selection or to the main mode.
Parameter
Value
Description
00.02*
9
Settings initialization
00.03
0
Start-up display selection
01.00
70.00
Maximum output frequency
01.16
4
Auto accel/decel
02.00
3
Source of first master frequency command: RS-485
02.01
4
Source of first operation command: RS-485
02.04
0
Motor direction control
02.07
1
Up/Down mode
02.09
0
Source of second frequency command
02.10
1
1st and 2nd master frequency command combination
02.11
40.0
Keypad frequency command
09.00
5
VFD communication address
09.01
1
Transmission speed: 9600 bps
09.02
3
Transmission fault treatment:keep operating
09.04
1
Communication protocol: ASCII 7, E, 1
* — after setting parameter 00.02 to 9, the VFD displays “End”, and
get back to the main indication mode (Fxxx). After this, continue setup
process from parameter 00.03.