Page 12
2.1
Gas Controls - Automatic Ignition (On/Off Burner*)
The heaters may be fitted with one of two types of gas control valves dependent upon the model,
each giving the same control elements as follows (see Section 4)
2.1.1
Main Gas Burner
The multifunctional main gas valve contains a gas regulator and two automatic shut off valves. When
set up as defined in Section 4 the valves will have a step opening operation on the main gas to give
smooth lighting. Settings of the valves are given in Section 4 and tables in Section 2.
2.1.2
Start Gas Burner
There is one solenoid valve to control the pilot burner gas supply which is designed to operate at inlet
pressure and therefore does not need a regulator.
* Note: For Modulating and High/Low burners, please refer to the Manual Supplement supplied.
2.2
Main Fan
The main air moving fan fitted to these appliances is operated automatically by the fan thermostat
within the Honeywell combination fan/limit thermostat and the Fan relay when in the heating mode or
the relevant relay for the current external demand when in the cooling mode.
2.3
Limit Thermostats
There are two limit thermostats on these heaters to protect them from overheating, should the air flow
fail for any reason. One is within the Honeywell combination thermostat and the second is situated on
the side of the heater towards the rear of the CUHD heater section.
2.3.1
Honeywell Combination Fan/Limit Thermostat
The combination fan/limit thermostat is a dual function control and safety device (see Fig. 2.2).
Fan Thermostat
The fan thermostat controls the operation of the main fan during the heater operating cycle. This
control also ensures that the main fan continues to run after the burner turns off to dissipate the
residual heat from the heat exchanger.
The white button on the fan thermostat should be pulled to its “out” position for normal operation. In
the “pushed in” position the fan will run continuously.
Limit Thermostat
The limit thermostat operates in overheat conditions caused by insufficient air passing over the heat
exchanger. This is a manual reset device and is reset by pressing in the red reset button on the
thermostat. Note the heat exchanger must have cooled to below the operating temperature for reset
to be possible.
Содержание Dualair DA260G Series
Страница 2: ...Details of condense drain for cooling coil ...
Страница 8: ...Page 6 Fig 2 1 DualAir 300 Module Dimensions Section 2 Technical Data FRONT VIEW REAR VIEW SIDE VIEW ...
Страница 9: ...Page 7 Fig 2 2 DualAir 380 Module Dimensions FRONT VIEW REAR VIEW SIDE VIEW ...
Страница 33: ...Page 31 Fig 5 1 Wiring for DualAir Units On Off Burner 230v Controls Section 5 Wiring Diagrams ...
Страница 34: ...Page 32 Fig 5 2 Wiring for DualAir Units On Off Burner 24v Controls ...
Страница 35: ...Page 33 Fig 5 3 Wiring for DualAir Units Hi Low Burner 230v Controls ...
Страница 36: ...Page 34 Fig 5 4 Wiring for DualAir Units Hi Low Burner 24v Controls ...
Страница 37: ...Page 35 Fig 5 6 Wiring for DualAir Units BMS Burner Modulation 230v Controls ...
Страница 38: ...Page 36 Fig 5 7 Wiring for DualAir Units BMS Burner Modulation 24v Controls ...
Страница 39: ...Page 37 Fig 5 7 Wiring for DualAir Units Full Burner Modulation 230v Controls ...
Страница 40: ...Page 38 Fig 5 8 Wiring for DualAir Units Full Burner Modulation 24v Controls ...
Страница 41: ......
Страница 42: ......
Страница 43: ......
Страница 44: ......
Страница 45: ......
Страница 46: ......
Страница 47: ......
Страница 48: ......
Страница 49: ......
Страница 50: ......