Button
Function
in the message display
in the menus
[Up]
If there are other older messages
present, they can be retrieved by
actuating this button (scroll through).
Previous menu entry.
[Down]
If there are other more recent mes-
sages present, they can be retrieved by
actuating this button (scroll through).
Next menu entry.
[Reset]
Deletes messages which are currently
saved.
● Aborts the chosen function and/or
exits the current menu level (ESC).
● If a submenu is active, you can
return to the main menu via
[Reset]
.
● In the main menu,
[Reset]
effects a
return to the message display (exit
the control menu).
[Reset PS]
Battery failures are cancelled (in so far
as they are no longer present).
● Activates the chosen function and/or
applies the settings (Enter).
● The submenu is activated if
[Reset]
is actuated in the main menu on an
entry that refers to a submenu.
● If no submenu exists, then activation
of the designation control function
occurs.
Tab. 3: Function of the control buttons
8.3
Display
The display serves to show, in text form, each of the current individual messages
that are pending. Moreover, the text display enables menu-guided operation of the
system.
8.3.1
Message display
Operating state
If there is no current message present, the message is shown in the display as per
The system’s operational readiness is dis-
played in the lowermost line by the '*' sign.
This sign runs cyclically from left to right
through the image. As soon as there is a
message present, the display changes
automatically into the basic state of the
message display.
Fig. 65: Display without messages
Display and control elements
Operating Instructions / DET-AC III Master / 916005 / 11-2022 / en_US