Extinguishing agent Novec
TM
1230
The extinguishing agent has been classified as slightly reactive to water. It must be
disposed of in accordance with all applicable local waste disposal regulations.
Observe the safety data sheet provided by the extinguishing agent’s manufacturer
3M
TM
.
The photolytic half-life of the extinguishing agent is 3 – 5 days. The global warming
potential (GWP) value is 1, while the value of the ozone decomposition potential
(ODP) is 0.
3.13
Behavior in the event of a fire
3.13.1
Preventive steps
● Always be prepared for fires and accidents!
● Keep first-aid equipment (first-aid kit, blankets, etc.) and substitute extinguishing
agents (e.g. fire extinguisher) in proper working order and readily available.
● Familiarize personnel with accident prevention, first aid and rescue equipment as
well as options for releasing the system manually.
● Keep access paths clear for rescue vehicles.
3.13.2
Steps in the event of a fire
L
WARNING
Risk of death due to fire!
Severe fire smoke may develop when a fire erupts and while the fire is being extin-
guished. Fire smoke development may result in severe airway damage or death.
● Keep the extinguishing zone closed in the event of a fire, e.g. do not open any
of the switch or server cabinet doors.
● After a fire, do not have the extinguishing zone opened by the safety officer
until the danger of re-ignition has subsided.
● Shut down all consumers of the power supply that are in the cabinet.
Take the following steps when a fire erupts:
● Initiate first-aid measures if necessary.
● Alert any endangered persons in the adjoining areas.
● Notify the fire department and/or emergency medical services.
● Notify the person in charge at the system's location.