18
PUB. NO. FASTRAXC FEBRUARY 2008
FASTRAX
™
THERMAL AIR SEAL BLOWER INSTALL
1.
Locate the 8’ flexible hose, attach to the thermal air seal
outlet and the wall with the cable ties and brackets
provided,
Figures 30 & 31.
2.
Route flexible hose to the best location to mount to the
blower with as few of bends as possible.
3.
Fasten blower to the wall and attach hose to blower,
Figures 30 & 31.
4.
Fasten Thermal Air System junction box to the wall and
wire blower.
OPERATE DOOR
1.
With curtain partially fed into the tracks, press the "OPEN"
button, when the door is at or near the open position, stop
and turn power off to the door and set the open limit
switch by rotating the open magnet arm until it lines up
with the open proximity switch. (XO i-COMM input should
illuminate)
2.
If the curtain travels past the jamb and/or out of the drive
gears, the brake handle will need to be tightened to
release the brake. Lower the curtain to the desired open
position, making sure curtain drive spheres are fed
equally level through the gears.
3.
Loosen brake handle to engage brake.
4.
With power on, turn open magnet arm until it lines up with
the open proximity switch (X0 i-COMM input should
illuminate).
5.
Press the green "OPEN" button, the door should travel
close.
6.
Stop and turn power off to the door when the curtain is at
or near the closed position. Rotate the closed magnet arm
until it lines up with the proximity switch. (X1 i-COMM
input should illuminate) Turn power on.
7.
Press the "OPEN" button and verify open limit is set
properly.
8.
Allow door to auto-reclose and verify closed limit is
properly set.
9.
Note the following for limit switch adjustments, (right and
left hand drive settings are the same),
Figure 32.
a.
Rotate open magnet clockwise to raise higher and
counter-clockwise to lower.
b.
Rotate closed magnet counter-clockwise to raise and
clockwise to lower.
NOTE: Each 1/2” of travel on the limit switch magnets is
equal to approximately 12” of curtain travel.
THERMAL AIR SYSTEM
FIGURE 31 - BLOWER
Ground Wire
Black Wire
#1 Motor Wire
White Wire
#2 Motor Wire
#1 Heater Wire
White or BLK #2 Wire
Curtain needs to be stopped at or before it reaches the top of the
jamb.
I M P O R T A N T ! ! !
FIGURE 32
Closed Limit Switch
Magnet (Red Dot)
Open Limit Switch Magnet
(Blue Dot)
Closed Limit
Switch (Red Dot)
Alternate Open
Limit Switch
Lower Photoeye
(18") Cut-Off Switch
Upper Photoeye
(54") Cut-Off Switch
Alternate Photoeye
(36") Limit Switch
Open Limit
Switch (Blue Dot)
For FasTrax FR door, if curtain has been sitting in the open
position for a period of time, allow the door to remain closed for a
couple of seconds to allow E-Vac system to remove air buildup.
I M P O R T A N T ! ! !
Содержание FASTRAX
Страница 13: ...PUB NO FASTRAXC FEBRUARY 2008 13 FASTRAX i COMM LOGIC CHART FIGURE 22 LOGIC CHART...
Страница 32: ...32 PUB NO FASTRAXC FEBRUARY 2008 FASTRAX VIRTUAL VISION ELECTRICAL WIRING...
Страница 36: ...36 PUB NO FASTRAXC FEBRUARY 2008 FASTRAX RADIAL ARCHITECTURAL DRAWING D O O R SYSTEM...
Страница 37: ...PUB NO FASTRAXC FEBRUARY 2008 37 FASTRAX VERTICAL ARCHITECTURAL DRAWING D O O R SYSTEM...
Страница 38: ...38 PUB NO FASTRAXC FEBRUARY 2008 FASTRAX STANDARD LIFT ARCHITECTURAL DRAWING D O O R SYSTEM...
Страница 39: ...PUB NO FASTRAXC FEBRUARY 2008 39 FASTRAX HIGH LIFT ARCHITECTURAL DRAWING D O O R SYSTEM...
Страница 40: ...40 PUB NO FASTRAXC FEBRUARY 2008 FASTRAX 45 TILT ARCHITECTURAL DRAWING D O O R SYSTEM...
Страница 41: ...PUB NO FASTRAXC FEBRUARY 2008 41 FASTRAX FR VERTICAL ARCHITECTURAL DRAWING D O O R SYSTEM...
Страница 42: ...42 PUB NO FASTRAXC FEBRUARY 2008 FASTRAX FR STANDARD ARCHITECTURAL DRAWING D O O R SYSTEM...
Страница 43: ...PUB NO FASTRAXC FEBRUARY 2008 43 FASTRAX FR HIGH LIFT ARCHITECTURAL DRAWING D O O R SYSTEM...
Страница 44: ...44 PUB NO FASTRAXC FEBRUARY 2008 FASTRAX FR 45 TILT ARCHITECTURAL DRAWING D O O R SYSTEM...