PUB. NO. FASTRAXC  FEBRUARY 2008   

27

FASTRAX

TROUBLESHOOTING

DEFINITION

FUNCTION

Activation

For activation questions, refer to the Activation Manual and inputs X5 & X6.

Brake

The brake is powered by 230VAC, if brake does not stop door when open or closing or if there is excessive 
noise, see brake adjustments on 

Page 21.

Breakaway

If the curtain is separated from the lower tracks, simply press the open button and the door will auto-refeed 
back into the tracks without tools or intervention.

Conduit Cable

If supplied conduit cable is too short, DO NOT splice wires, as the cable is shielded to prevent electrical noise 
from entering the control box i-COMM universal controller. Contact Aftermarket for replacement.

Curtain

The curtain is driven by the drive spheres and the drive tube.
a) If drive spheres are missing from curtain, repair or replace.
b) If curtain struggles to raise or lower or is baggy across the opening, verify tracks are proper distance: 
FasTrax = O.D.W. + 1/2” or FasTrax FR = O.D.W. + 9”.
c) Check to make sure tracks are lubricated with food grade synthetic grease (Super Lube).
d) If curtain is making contact with the wall when closing, verify lower tracks are not too close together.

Disconnect Switch

The disconnect switch is in line with fuse holder terminals F1, F2, F3, and removes power from the entire 
control box, except for terminals F1, F2, F3.

Drive Side Switch

The drive can be switched from right hand to left hand by performing the following:
a) Remove and switch conduit mounting bracket to opposite side.
b) Remove and switch motor mount bumper bracket.
c) Remove gearbox limit switch bracket and move to outside holes.
d) Remove and switch limit switch driven sprocket.
e) Remove and switch drive and non-drive photoeye cables.
f) New drive shroud is required.

Drive Tube

If drive spheres make excessive clicking noise, make sure tube drive gears are centered over track grooves.

FasTrax or FasTrax FR

FasTrax is the standard door and FasTrax FR is the freezer / cooler door with Thermal Air System.

i-COMM Controller™

The i-COMM controller is a circuit board that controls the actions of the door. There is a digital display that 
shows the cycles, status and position of the door at any time during its travel. For input and output function 
signals, refer to chart on 

Page 13.

Settings can be changed for re-close or pre-announce timers, interlocks, 

special activation commands, among many others, refer to instructional manual included.

Inverter

See 

Pages 14-15 

for proper parameter settings.

Limit Switches

The Open, Closed, and Photoeye limit switches are a normally open device and should only be closed when 
the magnet is in-line with the switch. If the switch is closed when it is not in-line with the magnet, check all plug
and pin connections to make sure they are not bent and/or replace the switch.
a) If the curtain travels past the open limit switch, dis-engage brake and turn drive tube to place bottom of 
curtain at the top of the jamb and set open limit by placing magnet at the open switch and verify X0 i-COMM 
input is on. Engage brake.
b) If the curtain travels past the close limit switch, dis-engage brake and turn drive tube to place bottom of 
curtain such that it seals the floor and set closed limit by placing magnet at the closed switch and verify X1

i-COMM input is on. Engage brake.

c) To adjust open limit switch, place door in the open position, and align magnet with the open limit switch, by 
rotating the open magnet plate.
d) To adjust the closed limit switch, lower door so the curtain bottom loop is sealing on the floor and align 
magnet with the close limit switch, by rotating the open magnet plate. 
e) Photoeyes are shut off as the door closes and the close magnet passes the photoeye cut-off switches.
f)  Operate door and test operation.
g) If limit switch chain jumps teeth, make sure it is lubricated.
h) If open and closed limit input LED’s are both on at the same time, the door will go into a fault.
j)  If door closes too far and does not see the closed limit switch, it will torque reverse, open and go into fault.

Module

The module is located on the cover of the motor junction box where the limit switches, photoeyes, optional 
I-Zone and cable from control box harness is wired.

Motor phasing

If "OPEN" button is pressed and the door closes, phasing is reversed, switch wires in terminals, V and W.

Non-Powered Opening

If issues arise with the non-powered opening chain hoist, check the following:
a) If power outage, release brake and pull chain on hoist to open door.
b) If chain hoist chain is pulled while door is powered, the door will go into fault mode (green light flashing).
c) If chain hoist chain is pulled, reset door by pressing the green flashing button. 

O.D.H. or O.D.W.

O.D.H. = Ordered Door Height or O.D.W. = Ordered Door Width

Open/Reset Push Button

The open/reset push button function is when the button is pressed, a command to open the door is given.

Pressure

If the curtain is blowing out because of high wind or negative pressures, check the following:
a) The tracks MUST be mounted at O.D.W. + 1/2” for FasTrax and O.D.W. + 9 1/2” for FR door. If mounted 
wider, excessive curtain wear may occur, if too narrow, curtain buckling or billowing will be greater.
b) Check to make sure the curtain has all the drive spheres in place.
c) Exterior doors are equipped with a garnet bag in the bottom loop to protect from the elements.
d) Stiffer track edging is standard on exterior doors.

Re-Close Timer

The door can be set to close from 2 to 255 seconds, follow i-COMM adjustment instructions.

Reversing Photoeye’s

The photoeyes are wired to the 24VDC circuit. They are wired as normally closed when there is power to the 
unit and the source photoeye is aligned with the receiver photoeye. The photoeye’s will reverse or hold the 
door open when the photoeye beam is blocked. When the beam is not broken, the door will auto-reclose. The 
photoeye’s will shut-off as the curtain closes.
a) Check to make sure lower track retention edging is not interfering with photoeye path.
b) Check to make sure lens of photoeye is free of debris such as dust, snow, ice, etc.
c) Emitter's are off when door is closed.
d) When open, i-COMM verifies photoeye inputs are off. If on, door will fault. If off, test is ok, emitter's turn on.
e) Verify module LED’s correspond with photoeye activation, LED on module should light up when close limit 

switch magnet is lined up with the photoeye cut-off switch at all 3 locations.

Virtual Vision

FasTrax FR door comes standard with Virtual Vision, when motion is sensed via Falcon motion sensors on the
opposite side of the curtain, the Virtual Vision red LED’s will illuminate to notify driver of movement on the 
opposite side of the curtain.
a) It is normal for the YDC3 output to flash on i-COMM during door operation.

Voltage Change

To change the voltage, see step below:
a) Change transformer taps, fuses, or overload settings per electrical diagram.
b) Change motor wiring per junction box diagram.
c) If door is powered by Inverter, then replace inverter.

Содержание FASTRAX

Страница 1: ...FASTRAX TM HIGH PERFORMANCE MODULAR DOOR PRINTED IN U S A Publication No FasTraxC email printshop RITEHITE com FEBRUARY 2008 This Manual Covers All Doors Shipped to Date...

Страница 2: ...RECOMMENDED SERVICE PARTS Bumper Rubber Motor 15250081 2 Fuse 1 Amp 250V Time Delay 51000002 2 Fuse 2 Amp 250V Time Delay 51000005 2 Kit Drive Sphere Qty 10 53700561 2 Closed Limit Switch 51950075 1 O...

Страница 3: ...oor place outside of vertical poly lumber pieces at 1 2 O D W 7 1 2 from centerline of opening Ordered Door Width Figures 2 2A or 3B 3 For FasTrax FR door place outside of vertical poly lumber pieces...

Страница 4: ...easure tracks at top and bottom to verify proper width 6 For High Vertical Lift or special configuration doors fasten the proper radius to the top of the lower track Figure 6 Page 9 DO NOT fully tight...

Страница 5: ...Door Width 1 2 1 8 0 FIGURE 3A FR LOWER TRACK W O POLY LUMBER FasTrax FR 1 2 Ordered Door Width 4 1 2 1 16 0 4 3 4 Ref Door Opening Width FasTrax FR Ordered Door Width 9 1 8 0 8 3 4 Ref FasTrax 1 2 O...

Страница 6: ...te to face of drive gear This dimension should be equal on both sides When distance is equal tighten bearing set screws Figure 10 5 Slide lock collar next to bearing and tighten lock collar set screws...

Страница 7: ...ign with the driven pulley on the limit switch assembly Sprocket DOES NOT require a key 4 Tilt limit switch assembly and install the chain over the sprockets The weight of the assembly as well as the...

Страница 8: ...rackets to upper track 7 Pilot holes 201 x 1 1 4 deep MUST be predrilled into lower track radius Make sure drill is perpendicular and level DO NOT drill into curtain groove 8 Repeat for opposite track...

Страница 9: ...4 deep MUST be predrilled into lower track radius Make sure drill is perpendicular and level DO NOT drill into curtain groove Figures 17 or 19 7 Fasten upper wall mount bracket to track and wall flush...

Страница 10: ...R TRACK INSTALLATION FIGURE 18 HIGH FasTrax O D W 5 1 2 1 8 0 FasTrax FR O D W 14 1 8 0 Upper Track Bracing Track Splice Wall Mounting Bracket O D H Ordered Door Height Radius Track Wall Mounting Brac...

Страница 11: ...l holes drilled through the control box must be through the bottom of the box Figure 21 8 Route all field installed wires so that separation is maintained between line voltage wires and low voltage cl...

Страница 12: ...12 PUB NO FASTRAXC FEBRUARY 2008 FASTRAX ELECTRICAL INSTALLATION FIGURE 21 CONTROL BOX Incoming Power Terminals F1 F2 F3 Incoming Power Terminals F1 F2 Serial Label Serial Label i COMM Controller...

Страница 13: ...PUB NO FASTRAXC FEBRUARY 2008 13 FASTRAX i COMM LOGIC CHART FIGURE 22 LOGIC CHART...

Страница 14: ...ameter being viewed before the M MODE key is pressed pressing the M MODE key will change the display to the parameter edit mode again This allows the user to very easily change between parameter view...

Страница 15: ...s O SPd Over speed Excessive motor speed typically caused by mechanical load driving the motor tunE Auto tune stopped before complete Run command removed before autotune complete It br I 2 t on brakin...

Страница 16: ...urtain and feed top drive sphere around the back side of the drive gear and into the radius and or track Figure 26 7 Rotate drive tube to drive curtain through the drive gears 8 Loosen brake release h...

Страница 17: ...ve Spheres FIGURE 27 FR CURTAIN Exhaust Cup Drive Side Top Curtain Roller Rear Top Seal FIGURE 28 FIGURE 30 THERMAL AIR SEAL Lower Track E Vac Cup E Vac Blower Hook Hose From Blower to Cup Optional Hi...

Страница 18: ...door should travel close 6 Stop and turn power off to the door when the curtain is at or near the closed position Rotate the closed magnet arm until it lines up with the proximity switch X1 i COMM inp...

Страница 19: ...m tube install top bolt only rotate tube outward approx 30 to line up install holes and temporarily insert bolt 6 Starting on the left side snap top of end center shroud piece angles into wall track a...

Страница 20: ...al Vision to Virtual Vision Cable Non Drive S F Emitter Photoeye J Box to Module Cable If Optional I Zone Present Additional 3 Plug Connector Will Be Present Drive S F Receiver Photoeye J Box to Modul...

Страница 21: ...late Be sure to get an equal gap at all three nut locations 6 To tighten the air gap raise the nuts just inside the red housing plate and then tighten the outside nuts BRAKE TORQUE ADJUSTMENT This sho...

Страница 22: ...at sensor To accomplish this temporarily disconnect the activation sensor s from its power supply at the I COMM use the remote to set a security code e g 1111 for the Virtual Vision sensor s then powe...

Страница 23: ...present at the track hole locations weld where possible Note There MUST be a fastener every other hole minimum approximately 4 3 Position upper weld plates so they catch the wall mount bracket holes...

Страница 24: ...f door height is less than 8 0 tall install drive guard onto radial style doors Figure 46 SIGN INSTALLATION 1 If door height is less than 8 0 tall install sign and brackets onto all radial style doors...

Страница 25: ...normal conditions Observe the door opening to make sure that it opens fully Observe the closing action to make sure that the door operates smoothly and fully closes without excessive curtain ripple at...

Страница 26: ...level fill with 90 weight if low Check snap rings to verify seated properly Check open and close positions adjust as required Check photoeye cutoff switches Lubricate chain sprockets and check alignme...

Страница 27: ...with the open limit switch by rotating the open magnet plate d To adjust the closed limit switch lower door so the curtain bottom loop is sealing on the floor and align magnet with the close limit swi...

Страница 28: ...RAM N A PRIOR 7822E004 7822E004 RITE HITE DOORS INC 9 1 D D EXTERNAL FIELD WIRING DIAGRAM 1744 XXXX RPB 9 6 2006 5288 2006 D UPDATE POWER TERMINALS 5594 1 30 2008 LIP B UPDATE I ZONE WIRING 5334 4 12...

Страница 29: ...PUB NO FASTRAXC FEBRUARY 2008 29 FASTRAX ACTIVATION WIRING 7822E011 7822E011 8 1 FasTrax SERIES ACTIVATION WIRING i COMM 1744 XXXX RPB 2 22 2007 5288 3 9 2007 2007...

Страница 30: ...J4 1 UNUSED 2 DC COMMON INPUT 0 VDC 3 DC POWER INPUT 24 VDC 4 24V AC INPUT 24 VAC 5 24V AC COMMON N 24 VAC 6 INVERTER COMMON 24 VDC 7 INVERTER OUTPUT K1 24 VDC 8 INVERTER OUTPUT K0 24 VDC J5 1 LOOP IN...

Страница 31: ...VDC 4 RESET INPUT X12 24 VDC J4 1 UNUSED 2 DC COMMON INPUT 0 VDC 3 DC POWER INPUT 24 VDC 4 24V AC INPUT 24 VAC 5 24V AC COMMON N 24 VAC 6 OPEN CLOSE COMMON 24 VDC 7 UNUSED 8 OPEN OUTPUT K0 24 VAC J5...

Страница 32: ...32 PUB NO FASTRAXC FEBRUARY 2008 FASTRAX VIRTUAL VISION ELECTRICAL WIRING...

Страница 33: ...ON JUNCTION BOX DWG NO 7822E009 7822E009 9 1 C C JBOX ASY VIRTUAL VISION 5357 XXXX RPB 2 7 2007 5288 3 9 2007 2007 A ADD NOTES 5326 5 4 2007 RPB B CORRECT VIRT VISION CABLE 5326 5 7 2007 RPB C REMOVE...

Страница 34: ...BY APPROVED BY DRAWN BY REF INITIAL ECN OVER 0 INCH TOLERANCES UP TO 0 125 5 1 25 40 80 15 0 25 1 25 15 40 5 FINISH 1 DEG 80 ANGLES 0 125 0 25 0 010 0 040 0 060 0 100 0 125 0 020 0 030 0 005 MM DD YY...

Страница 35: ...SCALE DRAWING DATE DATE DATE CHECKED BY APPROVED BY DRAWN BY REF INITIAL ECN OVER 0 INCH TOLERANCES UP TO 0 125 5 1 25 40 80 15 0 25 1 25 15 40 5 FINISH 1 DEG 80 ANGLES 0 125 0 25 0 010 0 040 0 060 0...

Страница 36: ...36 PUB NO FASTRAXC FEBRUARY 2008 FASTRAX RADIAL ARCHITECTURAL DRAWING D O O R SYSTEM...

Страница 37: ...PUB NO FASTRAXC FEBRUARY 2008 37 FASTRAX VERTICAL ARCHITECTURAL DRAWING D O O R SYSTEM...

Страница 38: ...38 PUB NO FASTRAXC FEBRUARY 2008 FASTRAX STANDARD LIFT ARCHITECTURAL DRAWING D O O R SYSTEM...

Страница 39: ...PUB NO FASTRAXC FEBRUARY 2008 39 FASTRAX HIGH LIFT ARCHITECTURAL DRAWING D O O R SYSTEM...

Страница 40: ...40 PUB NO FASTRAXC FEBRUARY 2008 FASTRAX 45 TILT ARCHITECTURAL DRAWING D O O R SYSTEM...

Страница 41: ...PUB NO FASTRAXC FEBRUARY 2008 41 FASTRAX FR VERTICAL ARCHITECTURAL DRAWING D O O R SYSTEM...

Страница 42: ...42 PUB NO FASTRAXC FEBRUARY 2008 FASTRAX FR STANDARD ARCHITECTURAL DRAWING D O O R SYSTEM...

Страница 43: ...PUB NO FASTRAXC FEBRUARY 2008 43 FASTRAX FR HIGH LIFT ARCHITECTURAL DRAWING D O O R SYSTEM...

Страница 44: ...44 PUB NO FASTRAXC FEBRUARY 2008 FASTRAX FR 45 TILT ARCHITECTURAL DRAWING D O O R SYSTEM...

Отзывы: