TEST RUN:
This menu point allows the user to check the settings of the PFC controller.
After activation of the test run, PFC checks if any fault condition present then
message will be displayed as INPUT FAULT TESTRUN ABORTED
For fault condition banks are not switched ON.
PFC switches each stage on and off successively and calculates the output of
the capacitors connected (this procedure is done three times to eliminate
possible errors).
kvar of capacitor bank can be seen while test run in process.
Any discrepancies in bank parameters found are evaluated and displayed in
plain text.
The following errors can be displayed:
UNSTABLE LOAD
CHECK CAPACITOR POWER!!!
CHECK CAPACITOR COUNT
Note: The results displayed are messages intended to help the user trace the
cause of the error. Final evaluation remains the responsibility of the user.
Under complicated (high load fluctuations) grid conditions, 100% error
recognition cannot be guaranteed.