DEFAULT SYSTEM VALUES
DEFAULT SYSTEM VALUES :
This menu allows user to reset PFC to factory
default setting.(Refer section 14 )
Press ENTER key to edit parameter.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.
During factory reset meter will display “WAIT”
message on second row then PFC will reset to factory
default settings.
Note :
- Resetting to factory default setting APFC will
initialize Energy, Demand counters and
resets Min / max values.
MAX SWITCH POWER
Press ENTER key to edit parameter.
Press UP or DOWN key to increments OR decrements
max switching power in steps of minimum bank kVAr
value. Then press ENTER key to confirm newly
changed max switching power.
MAX SWITCH POWER :
This menu allows user to set maximum capacitor
bank kVAr switching value.
The settable range is from minimum set capacitor
bank value upto the sum of total capacitor banks
values.
Increments in steps of minimum capacitor bank
value.
33