TEMPERATURE
RELAY ACTIVATION
Temperature : When cabinet temperature exceeds above
the 55 deg celsius PFC displays warning message and if
temperature exceeds above 60 deg celsius PFC
disconnects all the capacitor banks and activates the
relay if enabled.
RELAY ACTIVATION : PFC allows to activate / deactivate
assigned relay.
Press ENTER key to edit option.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.
Note :
- 1. If fault occurs PFC will Switch off all banks
including fixed banks one after the other with a delay of
1sec between the banks when fault occurs.
2. When temperature regains below the 55 deg celcius the
alarm relay gets deactivated and banks switching takes as
per requirement
3. The temperature limit of 55 and 60 deg celcius is factory
set and not editable.