VOLTAGE THD
TRIGGER VALUE
( 1 - 25 % )
RELAY ACTIVATION
VOLTAGE THD : When voltage THD is more
than set limit then PFC will operate alarm relay
Press ENTER key to enter into voltage THD sub setup.
Pressing UP or DOWN key will scroll through submenus.
TRIGGER VALUE : Value is settable from 1 to 25%.
Press ENTER key to edit trigger value.
Pressing UP or DOWN key will increment or decrement digit
value. Then pressing ENTER key will advance to next digit &
confirm newly changed values.
RELAY ACTIVATION : APFC unit allows to activate /
deactivate assigned relay.
Press ENTER key to edit option.
Press UP or DOWN key to get available options. Then
press ENTER key to confirm newly changed option.
Note :
- 1. If fault occurs PFC will Switch off all banks
including fixed banks one after the other with a delay of
1second.
2.Relay will reset at set trigger value of voltage THD minus
5%.
Reset point is factory set, not editable.