51
EMC enclosures that protect against electrical
interference which could cause a disturbance in
function.
2.
Avoid routing leads alongside cables and products that
are, or could be, a source of interference.
3.
To protect the product against permanent damage,
surge transients must be limited to 2kV pk. It is good
EMC practice to suppress differential surges to 2kV at
the source. The unit has been designed to automatically
recover in the event of a high level of transients.In
extreme circumstances it may be necessary to
temporarily disconnect the auxiliary supply for a period
of greater than 5 seconds to restore correct operation.
4.
ESD precautions must be taken at all times when
handling this product.
5.2 Case Dimension
5.3 Wiring
Input connections are made directly to screw-type terminals
with indirect wire pressure. Choice of cable should meet
local regulations. Terminal for both Current and Voltage
inputs will accept up to 2x 2.5mm² or 1x4mm² cables.