11
CONTROL PANEL HY.CELL
WIRE DIAGRAM
Control panel for 1 hydraulic bollard HYDRA serie.
Terminals
Function
Description
L-N-GND
Power supply
Input, 230VAC 50Hz (HY.CELL)
Input, 115VAC 50/60Hz (HY.CELL 115V))
(1-Phase/2-Neutral/GND-Ground connection)
1-2-3
Motor
Connection to the motor:
(1-lowering/2-common /3-raising)
6
Inf
Connection bollard status
DOWN
DOWN
Lowering command input (N.O. contact.),
programmable as clock contact
UP
UP
Raising command input (N.O. contact)
PHOT
PHOT
Safety devices input , N.C. contact (photocells, loop detectors ).
STOP
STOP
Input, STOP key (N.C. contact)
COM
COM
Common, all control inputs.
P.P.
Step-by-Step
Input, step-by-step key (N.O. contact).
In “Service man” mode, it activates the DOWN control function.
24 VAC
24Vac
Output, 24Vac/200mA max accessory power supply.
SCA
SCA/SYREN
Not insulated potential clean contact for the connection of a war-
ning light or an acoustic device.
See also DIP 4 functions
SHIELD-ANT
Antenna
Connection of the antenna to the incorporated radio-receiver module
(SHIELD-screen/ANT-signal).
Note:
The control unit uses a “P2” key with the same functions of the Step-by-Step push-button. This is useful
to control the automatic system during installation (only with DIP2: OFF).
TRIMMER FUNCTIONS
TW
It allows the maximum duration of raising and lowering.
It must be preset approx. 4s more with respect to the actual stroke time of the system.
The adjustment ranges from
6s
to
18s
maximum.
TCA
If activated , by meand of DIP 1, it allows to adjust a delay time for the automatic raising of the
bollard .
The adjustment ranges from 3s to 90s maximum.
12
DIP-SWITCH FUNCTION
Dip-Switches Function
Description
DIP1
TCA
Enable or disable the automatic raising of the bollard. The delay time
can be set by trimmer TCA.
On: Enable automatic raising
Off: disable automatic raising
DIP2
Preflashing
Enable or disable the lights of the bollard
DIP3
Fast automatic
raising
Enable or disable the fast automatic raising of the bollard (DIP1
must be ON).
On: Fast automatic raising activated . When the bollard is in lower
position , the intervention of the photocell causes the raising of the
bollard after 3 sec. If the intervention happens during the lowering
cycle of the bollard, the lowering cycle will be completed and after 3
sec. the bollard will do the raising cycle.
Off: Fast automatic raising not activated.
DIP4
SCA/SYREN
Select the operation mode of the output SCA/SYREN.
On: Warning acustic device, is activated during the raising cycle .
Off: Warinig light, it indicates the status of the bollard:
- Light on = bollard UP
- Fast flashing during raising cycle
- Slow flashing during lowering cycle
- Light off= bollard down
DIP5
Block keeping
See hereunder the paragraph “block keeping”
DIP6
Not used
RE-PRESSURISEING OF HYDRAULIC LOCKING
The re-pressuriseing of hydraulic locking function keeps the bollard in a stable UP position also when it
remains UP for long time.
This is a selectable function , it makes the bollard to do a short raising cycle that assure the correct UP
position of the bollard. The time intervals of the short raising cycles can be selected .
In order to activate this function it is necessary to put the DIP 5 in ON position. The green led light indicates
the time interval between the short raising cycles. The time interval can be selected by means of the push
button P1, hereunder you can see how to select the different time interval:
1 flash with pause
30 minutes
2 flashes with pause
1 hour (default)
3 flashes with pause
1 hour and 30 minutes
4 flashes with pause
2 hours
5 flashes with pause
2 hours and 30 minutes
6 flashes with pause
3 hours
7 flashes with pause
3 hours and 30 minutes
8 flashes with pause
4 hours
9 flashes with pause
4 hours and 30 minutes
10 flashes with pause
5 hours
11 flashes with pause
5 hours and 30 minutes
12 flashes with pause
6 hours
LED fixed ON
Deactivated function
After choosing the time interval put the DIP 5 in OFF position to confirm your selection.