Convector 460/560PTR
- 25 -
©Rinnai
10. Operational Flow Chart
Heater ON
Power Point ON
I
II
ON/OFF SW.
Normal
No
Yes
No
No
Yes
ON/OFF sw. ON
Yes
Operation/Comb. Ind.
Illuminates (Green)
Display time
6
Room temp.
A
R.F detection
sw.temp. fuse
Normal
III
T/C output
<10mV
No
No
No
Yes
Yes
Conv. motor Hi ON
Conv. motor Lo ON
Yes
Sparker ON
Solenoid SV1 ON
Solenoid SV2 ON
POV Med ON
(After 0.2 sec)
Overheat TH
Normal
Room Temp.
Thermistor
Normal
POV Hi ON
Yes
No
No
Yes
T/C output
(
Ú
1mV)
Operation/Comb. Indic.
Illuminates (Red)
Conv. motor med ON
Sparker OFF
Conv. motor Hi ON
Rev. flame detection
sw. OFF (150
E
C)
No
Yes
2
Temp. check starts
C.M. Mod. control
M.V modulating. control
OH Thermistor
activates (65
E
C)
Filter indicator flashes
Safety device
activated
No
No
Yes
(after approx. 3 sec.)
(30 sec. after (b))
(10 sec. after (c))
Ú
1 Igniton sensed
output is the initial T/C
check 2mV
(min.3mV. max. 18mV)
Fan motor error
<350rpm, 4 sec)
B
C.M med ON
Sparker OFF
Sparker OFF
Sparker OFF
(a)
(c)
73
Operation/Comb.
Ind. flashes (red)
71
Operation/Comb.
Ind. flashes (red)
70
Operation/Comb.
Ind. flashes (red)
14
Operation/Comb.
Ind. flashes (red)
Filter Ind. flashes
03
Operation/Comb.
Ind. flashes (red)
72
Operation/Comb.
Ind. flashes (red)
(After a max. of 50 sec)
33
Operation/Comb.
Ind. flashes (red)
34
31
Operation/Comb.
Ind. flashes (red)
32
Operation/Comb.
Ind. flashes (red)
11
62
Operation/Comb.
Ind. flashes (red)
12
Cause eliminated
Power Point OFF
All indicators OFF
ON/OFF Switch OFF
C.M. OFF
C.M. OFF
(After max.255 sec)
(Disconnection)
(Short circuit)
C.M. med ON
SV1,SV2 OFF
POV OFF
(Disconnection)
(Short circuit)
Conv. motor OFF
C.M. med OFF
SV1,SV2 OFF
POV OFF
(After 5 sec)
SV1, SV2 OFF
POV OFF
Conv. motor OFF
(150~255 sec)
14
Operation/Comb.
Ind. flashes (red)
Filter Ind. flashes
Thermal fuse
discon. (216
E
C)
OH thermistor
activated (70
E
C)
Gas disconn. device
when tilting is
activated (50~80
E
C)
03
Operation/Comb.
Ind. flashes (red)
Incomplete comb.
prevention safety
device is activated
(*mV, 5 sec)
12
Operation/Comb.
Ind. flashes (red)
OFF Function act.
>40
E
C 10 min
16
Operation/Comb.
Ind. flashes (red)
ON/OFF switch
Error (for 15 sec)
70
Operation/Comb.
Ind. flashes (red)
Re-instatement
of power
00
Operation/Comb.
Ind. flashes (red)
Power failure
Operation ceases
C.M Med ON
SV1, SV2 OFF
M.V POV OFF
C.M. med ON
LPG
NG
I: Micro-computer and E2PROM's signal path normal
II: Solenoid valve and Modulation valve rotation normal
III: Gas disconnection device normal when tilting
C.M.: Convection Motor
R.F.: Reverse Flame
SV: Solenoid
1
2
3
4
5
Fan motor
>6 r.p.m
6
62
Operation/Comb.
Ind. flashes (red)
10
11
9
5
5
PROP.G
5
9
2
10
3
12
11
1
Yes
(10 sec after (a))
C.M. OFF
No
Yes
5
7
8
8
9
(b)
16mV
14mV
16mV
*
Содержание RCE-460PTR
Страница 1: ...SERVICE MANUAL RCE 460PTR RCE 560PTR FAN CONVECTOR ...
Страница 16: ...Convector 460 560PTR 11 Rinnai 4 Dimensions Note All dimensions are in millimetres ...
Страница 17: ...Convector 460 560PTR 12 Rinnai 5 Installation The following clearances are recommended for installation ...
Страница 18: ...Convector 460 560PTR 13 Rinnai 6 Schematic Diagram ...
Страница 19: ...Convector 460 560PTR 14 Rinnai 7 Cut Away Diagram ...
Страница 20: ...Convector 460 560PTR 15 Rinnai 8 Operation Principles Control Panel Layout ...
Страница 29: ...Convector 460 560PTR 24 Rinnai ...
Страница 61: ...Convector 460 560PTR 56 Rinnai ...
Страница 62: ...Convector 460 560PTR 57 Rinnai ...
Страница 63: ...Convector 460 560PTR 58 Rinnai ...
Страница 64: ...Convector 460 560PTR 59 Rinnai ...
Страница 65: ...Convector 460 560PTR 60 Rinnai ...
Страница 66: ...Convector 460 560PTR 61 Rinnai ...
Страница 67: ...Convector 460 560PTR 62 Rinnai ...
Страница 68: ...Convector 460 560PTR 63 Rinnai ...
Страница 69: ...Convector 460 560PTR 64 Rinnai ...
Страница 70: ...Convector 460 560PTR 65 Rinnai ...