4.5 Cooling (Evaporative) Related – Group 1: {“ECOM”:
This group identifies evaporative cooling related information and is sent by the N-BW2 as part of the status
information reported when evaporative cooling is the current operating mode of the Networker System. In TABLE
4.5a below the “R” in the COMMAND column indicates read-only operation while a “W” indicates read/write
functionality.
GROUP2
COMMAND
Values
Description
{“CFG”: {
---
---
Configuration.
“ZUIS”: “$”
R
Y/N
Common Zone installed
Y
= Yes
N
= No
“ZAIS”: “$”
R
Y/N
Zone A installed
Y
= Yes
N
= No
“ZBIS”: “$”
R
Y/N
Zone B installed
Y
= Yes
N
= No
“ZCIS”: “$”
R
Y/N
Zone C installed
Y
= Yes
N
= No
“ZDIS”: “$”
R
Y/N
Zone D installed
Y
= Yes
N
= No
“TP”: “$”
R
Y/N
Display temperature
Y
= Yes
N
= No
{“GSO”: {
---
---
General System Operation
“SW”: “$”
W
F/N
Switched state
F
= Off
N
= On
“OP”: “$”
W
M/A
Operating state
M
= Manual
A
= Auto
“FS”: “$”
W
F/N
Fan state (Manual operation)
F
= Off
N
= On
“PS”: “$”
W
F/N
Pump state (Manual operation)
F
= Off
N
= On
“FL”: “##”
W
01 - 16
Fan speed level (01 – 16)
(Manual Operation)
“SP”: “##”
W
19 - 34
Comfort level (Set Point) (19 – 34)
(Auto Operation)
“ZUUE”: “$”
W
Y/N
Zone U user enabled
Y
= Yes
N
= No
“ZAUE”: “$”
W
Y/N
Zone A user enabled
Y
= Yes
N
= No
“ZBUE”: “$”
W
Y/N
Zone B user enabled
Y
= Yes
N
= No
“ZCUE”: “$”
W
Y/N
Zone C user enabled
Y
= Yes
N
= No
“ZDUE”: “$”
W
Y/N
Zone D user enabled
Y
= Yes
N
= No
{“GSS”: {
---
---
General System Status
“PW”: “$”
R
Y/N
Prewet action is active
Y
= Yes
N
= No
“BY”: “$”
R
Y/N
Cooler is busy
Y
= Yes
N
= No
“PO”: “$”
R
Y/N
Pump is being operated
Y
= Yes
N
= No
“FO”: “$”
R
Y/N
Fan is being operated
Y
= Yes
N
= No
“SN”: “$”
R
Y/N
Service notification
Y
= Yes
N
= No
“MT”: “###”
R
000 – 999
Measured temperature (x10). (999 indicates undefined)
“ZUAE”: “$”
W
Y/N
Zone U auto enabled
Y
= Yes
N
= No
“ZAAE”: “$”
W
Y/N
Zone A auto enabled
Y
= Yes
N
= No
“ZBAE”: “$”
W
Y/N
Zone B auto enabled
Y
= Yes
N
= No
“ZCAE”: “$”
W
Y/N
Zone C auto enabled
Y
= Yes
N
= No
“ZDAE”: “$”
W
Y/N
Zone D auto enabled
Y
= Yes
N
= No
Continued…