The following are the main dimensions when insalling some elements of the flue system:
The main minimum distances of respect, required by the technical Standard UNI 7129 for the correct positioning of
the exhaust terminals of appliances equipped with a fan with a thermal capacity between 16 and 35kW, are shown in
the table below:
A
C
D
B
M
N
L
H
I
G
E
F
DISTANCES FROM THE EXHAUST TERMINAL
(mm)
A
600
B
400
C
Below an opening used for ventilation/aeration
600
D
Horizontally to an opening used for ventilation
600
E
Below gutter
300
F
Vertically, from a terminal on the same wall
1500
G
Horizontally, from a terminal on the same wall
1000
H
Under a balcony
300
I
Horizontally from a balcony
1000
L
300
M
From ground or any walking area
2200
N
From any pipe or drain
300
Directly below a window
Horizontally to an opening
From the edge/recess/wall of the building
REU-1720FFU
200
145
150
220
125
100
Scarico a parete
Horizontal flue
ø 60/100
170
235
290
Condensate trap
ø 60/100
205
120
Split system
ø 80-80
(All dimensions in mm)