Vent Extension Installation Requirements
The following is an overview of guidelines and installation of Rinnai Direct
Vent Furnace vent extensions. This is not a substitute for any current
installation / owner’s manual or vent instructions
• The exhaust elbow assembly attached on the back of the unit must remain as a 90
°
elbow. Never bend
or straighten this component.
• Do not shorten the intake air hose attached to unit from factory.
This hose can never
be cut or altered in
length. The
extension that is
added to this hose
can be cut.
The exhaust elbow
exiting the unit should
never be straightened
(although it appears it
may be possible).